Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL REVIEW - FULL v.2
Permit Number - TC-COM-1224-02401
Review Name: COMMERCIAL REVIEW - FULL v.2
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 06/11/2025 | Commercial Building | APPROVED | Reviewer - Please see Internal Notes Structural(S) Reviewer (from previous submittal TUC9646001.123024) Madeline Nelson mnelson@safebuilt.com Approved Reason: Date Completed : 1/12/2025 11:42:33 AM Building(B) Reviewer Andrew Bevis abevis@safebuilt.com Approved Reason: Date Completed : 6/6/2025 12:40:13 PM |
||
| 06/11/2025 | Commercial Electrical | APPROVED | Reviewer - Please see Internal Notes Electrical(E) Reviewer Ron Ross rross@safebuilt.com Approved Reason: Date Completed : 6/6/2025 10:09:55 AM |
||
| 06/11/2025 | Commercial Mechanical | APPROVED | Reviewer - Please see Internal Notes Mechanical(M) Reviewer Jorge Valido jvalido@safebuilt.com Approved Reason: Date Completed : 6/10/2025 8:40:59 AM |
||
| 06/11/2025 | Outdoor Lighting | APPROVED | Reviewer - Please see Internal Notes Electrical(E) Reviewer Ron Ross rross@safebuilt.com Approved Reason: Date Completed : 6/6/2025 10:09:55 AM |
||
| 06/23/2025 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | Reviewer - Please see Internal Notes | ||
| 06/11/2025 | Commercial Plumbing | REQUIRES RESUBMIT | Reviewer - Please see Internal Notes Plumbing(P) Reviewer Perry Hendershott phendershott@safebuilt.com Denied Reason: Date Completed : 6/8/2025 11:41:48 AM SECOND PLUMBING REVIEW: COMMENTS 2, 7, 8, 9, 10 REMAIN RESOLVED-1). Plan Page A2.3 Rec Center roof: Small roof section that discharges to main roof will need an overflow scupper adjacent to the primary scupper.. Add an overflow supper adjacent o the primary scupper- 2018 IPC 1106.5, 1108 UN-RESOLVED-2). Plan Page A4.0 Maintenance Roof Plan: Missing overflow suppers adjacent o the primary scuppers.. Add an overflow scuppers adjacent to the primary scuppers- 2018 IPC 1106.5, 1108 **OVERFLOW NEEDS TO BE IN PARAPET WALL, ADJACENT & SEPARATE** RESOLVED-3). Plan Page P6.1 & P6.2: The dual P4M washer drains need lint trap(s). Add Lint trap(s) to the dual P4M Washer drains. -2018 IPC 1003.6 RESOLVED-4). Plan Page P2.3 Rec Bldg: Missing primary/secondary roof drains, roof drain conductors & roof drain conductor termination illustrations along with sizing calculations for the Rec bldg. Add the primary/secondary roof drains, roof drain conductors & roof drain conductor termination illustrations along with sizing calculations for the Rec bldg., will need to correlate with plan page A2.3 - 2018 IPC 1106.1, 1106.2, 1108 RESOLVED-5). Plan Page P2.2 detail 1: The P6c fixture indicator in the utility/maintenance room is incorrect. Update the fixture indicator to correlate with fixture schedule on plan page P5.2 -2018 IPC 106.3.1 RESOLVED-6). General: Missing Gas Plans for Ramada BBQ as shown on on plan page A4.1 and gas plans for any other gas accessories/features. Provide Gas Plans for Ramada BBQ as shown on on plan page A4.1 and gas plans for any other gas accessories/features -2018 IFGC 106.3.1 NEW COMMENT-7). Plan Page P2.3 Rec Bldg: Missing primary/secondary roof drains, roof drain conductors & roof drain conductor sizing calculations for the Rec bldg LOBBY AREA. Add the primary/secondary roof drains, roof drain conductors & roof drain conductor sizing calculations for the Rec bldg LOBBY AREA., - 2018 IPC 1106.1, 1106.2, 1108 NEW COMMENT -8).NEW PLAN SHEET P2.4: Missing gas sizing table & total system legnth. Add gas sizing table & total system legnth -2018 IFGC 402.3 New Comment 9). NEW PLAN SHEET P2.4: Missing exhaust & combustion air information & illustration for the pool heaters. Add exhaust & combustion air information & illustration for the pool heaters.-2018 IFGC 302 & 503.1 **note: not shown in mech pages either** NEW COMMENT 10). PLAN PAGE P2.3: MISSING MOP SINK INDICATOR P4C. ADD MOP SINK INDICATOR P4C. -2018 IPC 106.3 |
||
| 06/20/2025 | Fire New Construction | REQUIRES RESUBMIT | -Correct applicable codes, sheet T1.0. TFD adopted the 2024 IFC (9/24). You also listed NWFD amendments. Please remove any reference to NWFD. -Could not locate your updated comments regarding the fire alarm. Please update to show your intentions of installing a fire alarm in required buildings. john.vincent@tucsonaz.gov 5203495581 |
||
| 06/20/2025 | Site Engineering | REQUIRES RESUBMIT | TC-COM-1224-02401 1767 E BENSON HY Site Engineering Comments are as follows: - Site Engineering has reviewed the building plans for compliance with Development Package (DP) TD-DEV-1224-00324, this permit can not be approved until the DP is approved by all review agencies. marco.contreras@tucsonaz.gov |
||
| 06/23/2025 | Site Zoning | REQUIRES RESUBMIT | Reviewer - Please see Internal Notes FROM: PDSD Zoning Review Section PROJECT: BLDG 1 = TC-COM-1224-02384, BLDG 2 = TC-COM-1224-02401, BLDG 3 = TC-COM-1224-02402, BLDG 4 =TC-COM-1224-02403, BLDG 5 = TC-COM-1224-02404, BLDG 6 = TC-COM-1224-02405, BLDG 7 = TC-COM-1224-02406, BLDG 8 = TC-COM-1224-02407, BLDG 9 = TC-COM-1224-02408, COVERED PARKING CANOPIES = TC-COM-1224-02409 - TD-DEV-1224-00324 1767 E BENSON HY. - C-2 Multifamily (2nd Review) TRANSMITTAL DATE: ‎June 23, 2025 COMMENTS: Resubmit revised drawings along with a detailed response letter, which states how all Zoning Review Section comments were addressed. This site is located in C-2 zone (UDC 4.7.24). Multifamily Use is a permitted use in the zone (UDC Table 4.8-4) 1. Zoning has reviewed the building plans for compliance with Development Package (DP) TD-DEV-1224-00324, and although it appears that the plans match until the DP is approved by all review agencies Zoning cannot approve the building plans. 2. The Parking Requirements shown on sheet T3.0 does not match what is shown on DP TD-DEV-1224-00324. Either ensure that the calculation match or remove the calculation from the building plans. 3. The Parking Units shown on sheet T1.0 shows a total of 388 parking units for the site but the DP shows 391 space provided. Clarify which is correct and ensure that the plans match or remove the calculation from the building plans. 4. The gross floor area listed in the Hud Apartment Tabulation sheet T1.0 for buildings 2-8, 26,655 GFA, does not match what is shown within the footprint of the buildings on the DP. Clariy which is correct and ensure the plans match. 5. The gross floor area listed in the Hud Apartment Tabulation sheet T1.0 for the recreation building, 2,803 GFA, does not match what is shown within the footprint of the building on the DP. Clariy which is correct and ensure the plans match. If you have any questions about this transmittal, please contact Zone1.desk@tucsonaz.gov. |
||
| 06/05/2025 | PDSD Application Completeness Express | REVIEW COMPLETED | Reviewer - Please see Internal Notes |