Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
01/16/2025 | Outdoor Lighting | NOT REQUIRED | No exterior lighting modifications. Outdoor lighting to remain as-is. | ||
N/A | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
N/A | Historic Standard | PENDING ASSIGNMENT | |||
N/A | Site Zoning | PENDING ASSIGNMENT | |||
01/28/2025 | Addressing Validation | REQUIRES RESUBMIT | Address has Multiple suites. Building and Suite Number will have to be confirmed and assigned to Permit Application and on Plans. Please submit a comment letter and Plans (with the suite#). If you're uncertain about suite# please contact Pima County Addressing at Addressing@pima.gov or 520-724-9512 | ||
01/23/2025 | Commercial Building | REQUIRES RESUBMIT | Please submit your revised documents and provide a letter with a written response letter addressing each of the comments indicating how the Review comments were resolved. 1. Please amend plans to provide a detailed description of the work involved in this permit’s scope. IBC 105.3 2. Sheet G002: Please amend the plans to provide a summary of the code analysis as follows to ensure the C of O information matches the design and drawings. IBC 107.2.1: A. The use and occupancy, in accordance with the provisions of Chapter 3. For example, A-2, B, etc. B. The type of construction as defined in Chapter 6. For example, VB C. The design occupant load. For example, 289 D. If an automatic sprinkler system is provided, whether the sprinkler system is required. E. Total Square footage of Occupied Spaces 3. Sheet G-002: Please amend plans to identify the accessible entrances with at least 60% of the entrances are accessible. IBC 1105.1 Additionally, provide directional signage for any inaccessible entrances. IBC 111.2 4. Sheet G-002: Please review plumbing fixture count as it appears 12 water closets would be required 5 for men and 7 for women IBC Table 2902.1 5. Sheet G-002: Please apply for an Appeal to the Building Official to allow the use of both water closets and lavatory fixtures for use by all persons regardless of sex as the 2018 IBC 2902.2 requires separate facilities for each sex. 6. Sheet S101.1: Please provide Geotechnical Engineer’s findings and Soils report with your next submittal as required by Foundation Note 2 IBC 107.2.1 7. Please provide a special inspection certificate with Part A, and Part B, completed with next submittal. IBC 107.2.1 https://www.tucsonaz.gov/files/sharedassets/public/v/1/city-services/planning-development-services/documents/special_inspection_certificate.pdf 8. Please amend plans to show the current edition of the adopted codes and referenced standards. IBC 107.2.1 Treat as a typical note. For example, A. S101.1 Please amend to reference the current adopted code as Foundation Note 1. Indicates 2012 IBC B. S101.2 Structural Steel Notes 11&12 indicate AWS D1.1 2015 and the 2018 IBC references appear to be AWS D1.4/D1.4M—2017 9. Sheet S101.3: Please list the special inspections required for this project IBC 107.2.1 For example, Post installed anchors. 10. Sheet A-103: Please show the accessible route connecting level 1 to Green Room and adjacent restroom with new tiled shower. IBC 1104.2 11. Sheet A-103: Please provide dimensioned construction drawings and details for new custom tiled shower adjacent to Geen Room and show accessibility compliance. IBC 107.2.1 12. Sheet A-601: Please amend plans to provide a door hardware schedule for each door. IBC 107 13. IEBC 305.7 requires that accessibility be provided to the altered spaces. Where the existing path of travel elements, which entails a primary entrance, a primary path of travel, sanitary facilities serving the area, a drinking fountain, and signs. If these items are in full compliance with the current code, provide a statement indicating this on the cover sheet of the drawings. Otherwise, accessibility upgrades shall be required in accordance with IEBC.305.7. 1. If the cost of providing or upgrading the items above to be accessible is disproportionate to the cost of construction (exceeds 20% of the cost of construction not including accessibility upgrades), please provide information to verify construction costs. (A) Alterations made to provide an accessible path of travel to the altered area will be deemed disproportionate to the overall alteration when the cost exceeds 20% of the cost of the alteration to the primary function area. (B) Costs that may be counted as expenditures required to provide an accessible path of travel may include: For example, costs associated with making restrooms accessible, such as installing grab bars, enlarging toilet stalls, insulating pipes, or installing accessible faucet controls. Please contact me if you have any questions about these comments. Mark Masek Plans Examiner – Building Safety Planning and Development Services | City of Tucson main 520.837.4994 email mark.masek@tucsonaz.gov |
||
01/15/2025 | Commercial Electrical | REQUIRES RESUBMIT | Commercial Electrical Review TC-COM-1224-02396 (800 N COUNTRY CLUB RD Unit:BLDG 1 TUCSON, AZ 85716) Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received. Code reference, 2018 International Building Code (IBC), 2017 National Electrical Code (NEC). 1. Designate the circuit number at the location of each, receptacle, appliance, and equipment disconnect switch, E3404.12. >>> Electrical outlets on Performing Arts – 1st Floor Power Plan, sheet E201, are all missing circuit/panel designations. >>> Lighting outlets, on sheet E301, are missing circuit/panel designations. >>> Fire Alarm circuits, on sheet E401, are missing circuit/panel designations. 2. Provide an electrical panel schedule showing panel size, circuit numbers, ampacity, wire size and general description for each new or modified circuit, NEC 110.22(A) & 408.4(A). >> Panel schedules for Panels CB and CY show no loads. Please clarify if there are new loads in these panels. 3. Show the location of Panel TB and the associated recepticals on the electrical plans. Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov |
||
01/23/2025 | Commercial Mechanical | REQUIRES RESUBMIT | 1. Provide heating and cooling load calculations to justify the heating/cooling capacity of the specified HVAC unit, CB1. Reference: Sections C403.1.1 and C502.2.3, IECC 2018. 2. Show that the walk-in cooler meets the construction requirements of Section C403.10.2, IECC 2018. 3. Show that the walk-in cooler meets the efficiency requirements of Section C403.10.2.1, IECC 2018. |
||
01/22/2025 | Commercial Plumbing | REQUIRES RESUBMIT | 1. The substitution of urinals for a maximum of 67% of the water closets applies only to the water closets designated for men. Based on your calculations, in separate facilities, there would be 7 water closets for women and 5 water closets for men. With 2 water closets and 3 urinals for the men, you still require 7 water closets for the women (one of which can be used for the required family restroom, Section 1109.2.1, IBC 2018). Reference: Section 424.2, IPC 2018. 2. Clarify the note on sheet P-100, “Connect new 2-1/2” CW to existing 2” CW downstream of SOV.” The drawing appears to show a new 2” CW and an existing 2-1/2” CW. On sheets P-101 the “new” line is labeled as 2” and on P-202, it is labeled as 2-1/2” CW. |
||
01/28/2025 | Historic | REQUIRES RESUBMIT | This property is a Historic Landmark, requires review by PRS. Please apply for historic sub record. Attached is a link on how to get to the sub-record. https://www.tucsonaz.gov/files/sharedassets/public/v/2/pdsd/documents/tdc-faq/new-pdfs/sub-records.pdf Alternatively, The following resource to help you apply for the sub-record: sub-records.pdf If you have any questions, contact Michael.Taku@tucsonaz.gov |
||
01/23/2025 | Site Engineering | REQUIRES RESUBMIT | 1. As outdoor work is included in this submittal (landscaping, irrigation, etc.), a development package is required and must be approved before this building permit can be approved. Mike Ortiz michael.ortiz@tucsonaz.gov |
||
01/22/2025 | Water - PDSD | REQUIRES RESUBMIT | Provide the size of the water meter serving this activity, the size of the backflow preventer associated with the water meter, and the total water demand served by the water meter. Reference: Section 107.2.1, IBC 2018. | ||
01/14/2025 | Fire New Construction | REVIEW COMPLETED | |||
12/31/2024 | PDSD Application Completeness Express | REVIEW COMPLETED |