Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL REVIEW - FULL v.1
Permit Number - TC-COM-1224-02388
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
01/17/2025 | Site Zoning | APPROVED | |||
01/16/2025 | Water - PDSD | APPROVED | |||
01/17/2025 | Site Landscape | NOT REQUIRED | |||
01/31/2025 | Site Landscape Standard | NOT REQUIRED | |||
01/31/2025 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
01/30/2025 | Commercial Building | REQUIRES RESUBMIT | January 8, 2025 1st Review Seaver Franks Architects Attn: Rick Huch/Daren Sadowsky 2552 N. Alvernon Way Tucson, Arizona 85712 Re: STARR PASS MARRIOTT – SWING SUITE TENANT IMPROVEMENT City of Tucson Permit Number: TC-COM-1224-02388 Stantec Project Number: 185215066 Stantec File Number: TUC-24-159 Plan review for the above referenced project has been completed. This letter reflects comments to be addressed. PLEASE send all response to comments back to the City through the permit portal! Responses sent directly to Stantec will be ignored. Also, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed. Please cloud and delta all changes and provide a letter with a written response to each of the comments indicating the action taken. The scope of this review covers the architectural, plumbing, mechanical, and electrical designs as they relate to the codes adopted by the jurisdiction. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions, and concerns before permit approval. Occupancy Group Construction Type Area (Square feet) Occupant Load Automatic Fire Sprinklers Fire Alarms A-3 I-B 1,030 N/A Yes Yes Separate Permits: Automatic fire sprinklers and fire alarm. Deferred Submittals: None. Special Inspections: None. ARCHITECTURAL COMMENTS Sheet A0.0 1. The code analysis indicates the occupancy as a Group A-2. The proposed swing suite would classify more as a Group A-3 occupancy as the proposed use is now more for recreation/amusement rather than food/drink consumption. Please revise. [Ref. IBC 2018 Sec. 303.4] 2. Please provide an updated occupant load for the new use of the space. [Ref. IBC 2018 Sec. 1004.5] STRUCTURAL COMMENTS There are no comments. MECHANICAL COMMENTS There are no comments. PLUMBING COMMENTS There are no comments. ELECTRICAL COMMENTS There are no comments. Should you have any questions regarding the plan review comments, please contact the plan reviewer listed for the appropriate discipline. Plans reviewed by: Trevor Bies, Senior Plan Reviewer 602-338-9922 trevor.bies@stantec.com |
||
01/30/2025 | Commercial Electrical | REQUIRES RESUBMIT | January 8, 2025 1st Review Seaver Franks Architects Attn: Rick Huch/Daren Sadowsky 2552 N. Alvernon Way Tucson, Arizona 85712 Re: STARR PASS MARRIOTT – SWING SUITE TENANT IMPROVEMENT City of Tucson Permit Number: TC-COM-1224-02388 Stantec Project Number: 185215066 Stantec File Number: TUC-24-159 Plan review for the above referenced project has been completed. This letter reflects comments to be addressed. PLEASE send all response to comments back to the City through the permit portal! Responses sent directly to Stantec will be ignored. Also, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed. Please cloud and delta all changes and provide a letter with a written response to each of the comments indicating the action taken. The scope of this review covers the architectural, plumbing, mechanical, and electrical designs as they relate to the codes adopted by the jurisdiction. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions, and concerns before permit approval. Occupancy Group Construction Type Area (Square feet) Occupant Load Automatic Fire Sprinklers Fire Alarms A-3 I-B 1,030 N/A Yes Yes Separate Permits: Automatic fire sprinklers and fire alarm. Deferred Submittals: None. Special Inspections: None. ARCHITECTURAL COMMENTS Sheet A0.0 1. The code analysis indicates the occupancy as a Group A-2. The proposed swing suite would classify more as a Group A-3 occupancy as the proposed use is now more for recreation/amusement rather than food/drink consumption. Please revise. [Ref. IBC 2018 Sec. 303.4] 2. Please provide an updated occupant load for the new use of the space. [Ref. IBC 2018 Sec. 1004.5] STRUCTURAL COMMENTS There are no comments. MECHANICAL COMMENTS There are no comments. PLUMBING COMMENTS There are no comments. ELECTRICAL COMMENTS There are no comments. Should you have any questions regarding the plan review comments, please contact the plan reviewer listed for the appropriate discipline. Plans reviewed by: Trevor Bies, Senior Plan Reviewer 602-338-9922 trevor.bies@stantec.com |
||
01/30/2025 | Commercial Mechanical | REQUIRES RESUBMIT | January 8, 2025 1st Review Seaver Franks Architects Attn: Rick Huch/Daren Sadowsky 2552 N. Alvernon Way Tucson, Arizona 85712 Re: STARR PASS MARRIOTT – SWING SUITE TENANT IMPROVEMENT City of Tucson Permit Number: TC-COM-1224-02388 Stantec Project Number: 185215066 Stantec File Number: TUC-24-159 Plan review for the above referenced project has been completed. This letter reflects comments to be addressed. PLEASE send all response to comments back to the City through the permit portal! Responses sent directly to Stantec will be ignored. Also, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed. Please cloud and delta all changes and provide a letter with a written response to each of the comments indicating the action taken. The scope of this review covers the architectural, plumbing, mechanical, and electrical designs as they relate to the codes adopted by the jurisdiction. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions, and concerns before permit approval. Occupancy Group Construction Type Area (Square feet) Occupant Load Automatic Fire Sprinklers Fire Alarms A-3 I-B 1,030 N/A Yes Yes Separate Permits: Automatic fire sprinklers and fire alarm. Deferred Submittals: None. Special Inspections: None. ARCHITECTURAL COMMENTS Sheet A0.0 1. The code analysis indicates the occupancy as a Group A-2. The proposed swing suite would classify more as a Group A-3 occupancy as the proposed use is now more for recreation/amusement rather than food/drink consumption. Please revise. [Ref. IBC 2018 Sec. 303.4] 2. Please provide an updated occupant load for the new use of the space. [Ref. IBC 2018 Sec. 1004.5] STRUCTURAL COMMENTS There are no comments. MECHANICAL COMMENTS There are no comments. PLUMBING COMMENTS There are no comments. ELECTRICAL COMMENTS There are no comments. Should you have any questions regarding the plan review comments, please contact the plan reviewer listed for the appropriate discipline. Plans reviewed by: Trevor Bies, Senior Plan Reviewer 602-338-9922 trevor.bies@stantec.com |
||
01/30/2025 | Commercial Plumbing | REQUIRES RESUBMIT | January 8, 2025 1st Review Seaver Franks Architects Attn: Rick Huch/Daren Sadowsky 2552 N. Alvernon Way Tucson, Arizona 85712 Re: STARR PASS MARRIOTT – SWING SUITE TENANT IMPROVEMENT City of Tucson Permit Number: TC-COM-1224-02388 Stantec Project Number: 185215066 Stantec File Number: TUC-24-159 Plan review for the above referenced project has been completed. This letter reflects comments to be addressed. PLEASE send all response to comments back to the City through the permit portal! Responses sent directly to Stantec will be ignored. Also, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed. Please cloud and delta all changes and provide a letter with a written response to each of the comments indicating the action taken. The scope of this review covers the architectural, plumbing, mechanical, and electrical designs as they relate to the codes adopted by the jurisdiction. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions, and concerns before permit approval. Occupancy Group Construction Type Area (Square feet) Occupant Load Automatic Fire Sprinklers Fire Alarms A-3 I-B 1,030 N/A Yes Yes Separate Permits: Automatic fire sprinklers and fire alarm. Deferred Submittals: None. Special Inspections: None. ARCHITECTURAL COMMENTS Sheet A0.0 1. The code analysis indicates the occupancy as a Group A-2. The proposed swing suite would classify more as a Group A-3 occupancy as the proposed use is now more for recreation/amusement rather than food/drink consumption. Please revise. [Ref. IBC 2018 Sec. 303.4] 2. Please provide an updated occupant load for the new use of the space. [Ref. IBC 2018 Sec. 1004.5] STRUCTURAL COMMENTS There are no comments. MECHANICAL COMMENTS There are no comments. PLUMBING COMMENTS There are no comments. ELECTRICAL COMMENTS There are no comments. Should you have any questions regarding the plan review comments, please contact the plan reviewer listed for the appropriate discipline. Plans reviewed by: Trevor Bies, Senior Plan Reviewer 602-338-9922 trevor.bies@stantec.com |
||
01/30/2025 | Outdoor Lighting | REQUIRES RESUBMIT | January 8, 2025 1st Review Seaver Franks Architects Attn: Rick Huch/Daren Sadowsky 2552 N. Alvernon Way Tucson, Arizona 85712 Re: STARR PASS MARRIOTT – SWING SUITE TENANT IMPROVEMENT City of Tucson Permit Number: TC-COM-1224-02388 Stantec Project Number: 185215066 Stantec File Number: TUC-24-159 Plan review for the above referenced project has been completed. This letter reflects comments to be addressed. PLEASE send all response to comments back to the City through the permit portal! Responses sent directly to Stantec will be ignored. Also, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed. Please cloud and delta all changes and provide a letter with a written response to each of the comments indicating the action taken. The scope of this review covers the architectural, plumbing, mechanical, and electrical designs as they relate to the codes adopted by the jurisdiction. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions, and concerns before permit approval. Occupancy Group Construction Type Area (Square feet) Occupant Load Automatic Fire Sprinklers Fire Alarms A-3 I-B 1,030 N/A Yes Yes Separate Permits: Automatic fire sprinklers and fire alarm. Deferred Submittals: None. Special Inspections: None. ARCHITECTURAL COMMENTS Sheet A0.0 1. The code analysis indicates the occupancy as a Group A-2. The proposed swing suite would classify more as a Group A-3 occupancy as the proposed use is now more for recreation/amusement rather than food/drink consumption. Please revise. [Ref. IBC 2018 Sec. 303.4] 2. Please provide an updated occupant load for the new use of the space. [Ref. IBC 2018 Sec. 1004.5] STRUCTURAL COMMENTS There are no comments. MECHANICAL COMMENTS There are no comments. PLUMBING COMMENTS There are no comments. ELECTRICAL COMMENTS There are no comments. Should you have any questions regarding the plan review comments, please contact the plan reviewer listed for the appropriate discipline. Plans reviewed by: Trevor Bies, Senior Plan Reviewer 602-338-9922 trevor.bies@stantec.com |
||
01/08/2025 | Fire New Construction | REVIEW COMPLETED | |||
12/27/2024 | PDSD Application Completeness Express | REVIEW COMPLETED | |||
01/21/2025 | Site Engineering | REVIEW COMPLETED |