Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: TC-COM-1224-02384
Parcel: 13216012Q

Address:
1767 E BENSON HY

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.4

Permit Number - TC-COM-1224-02384
Review Name: COMMERCIAL REVIEW - FULL v.4
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
02/20/2026 Bldg Permits - Post Review Express PENDING ASSIGNMENT
02/20/2026 Fire New Construction REQUIRES RESUBMIT 1. Sheet T1.0, deferred submittals. You currently show automatic fire sprinkler system and fire sprinkler systems. This is the same thing. Remove one of these.
2. It appears you are only installing a dedicated fire alarm system (sprinkler monitoring) for the apartments and a building fire alarm system for the clubhouse. According to IFC 907.2.9, every apartment building and clubhouse will need a full fire alarm system, not just sprinkler monitoring. Please explain.
3. Add to the cover sheet, separate submittal for the fire alarm. Fire alarm shall comply with IFC and NFPA 72. Please call if you need guidance. It needs to be understood that all buildings need a fire alarm and not just sprinkler monitoring. Fire alarm panels need to be located in a conditioned space if there will be a panel for every building.
john.vincent@tucsonaz.gov
5203495581
02/12/2026 Site Engineering REQUIRES RESUBMIT Permit: TC-COM-1224-02384
Location: 1767 E BENSON HY
Review Date: 2/12/2026
Site Engineering Comments:
1. While Site Engineering has reviewed the plan set in compliance with the associated development package, permit TC-COM-1224-02384 cannot be approved until the associated development package TD-DEV-1224-00324 is reviewed and approved by all reviewers.

If you have any questions or concerns, please contact
Marco Contreras
Marco.contreras@tucsonaz.gov
02/20/2026 Site Zoning REQUIRES RESUBMIT PDSD TRANSMITTAL

FROM:
Bobby Parsons
PDSD Zoning Review Section

PROJECT:
TC-COM-1224-02384 - TD-DEV-1224-00324
1767 E. Benson Hwy. Tucson, AZ 85714
New Apartment Community – BLDG. 1/Recreation Bldg (4th Review)

TRANSMITTAL DATE: 2/20/2026

Comment: Please resubmit revised drawings along with a detailed response letter which states how all Zoning Review Section comments were addressed.

This site is located in the C-2 zone (UDC 4.7.21). Multifamily is a permitted use in this zone (UDC Table 4.8-4).

1. Comment: Site Zoning has reviewed the building plans for compliance with the associated Development Package (DP) TD-DEV-1224-00324. While it appears the building plans match the DP, Site zoning cannot approve this permit until the DP is approved by all review agencies.
2. Comment: Additional comments may be forthcoming depending on responses to zoning review comments and plans submitted.

If you have any questions about this transmittal, please contact Bobby Parsons at Robert.Parsons@tucsonaz.gov.
02/05/2026 PDSD Application Completeness Express REVIEW COMPLETED