Permit Number: TC-COM-1224-02378
Parcel: 125010020

Address:
950 N TUCSON BL

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - LIMITED v.1

Permit Number - TC-COM-1224-02378
Review Name: COMMERCIAL REVIEW - LIMITED v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
01/13/2025 Commercial Plumbing APPROVED
01/13/2025 Water - PDSD APPROVED
01/31/2025 Bldg Permits - Post Review Express PENDING ASSIGNMENT
01/14/2025 Commercial Building REQUIRES RESUBMIT ACTIVITY NO. TC-COM-1224-02378
ADDRESS/PARCEL: (950 N TUCSON BL TUCSON, AZ 85716)
Submit your revised drawings along with a detailed response letter, which states how all Building Review Section comments were addressed. The submitted documents were incomplete and a thorough plan review could not be performed. Please be aware, new comments may arise with the next review. Review will not proceed without the response letter.
COMMENTS:
1. Please provide information for the following:
a. Awnings & canopies shall comply to the fire propagation performance criteria Test 1 or 2 of NFPA 701 and Flame Spread Index not greater than 25 per ASTM E84 or UL 723 and comply to NFPA 286 per IBC 3105.3
b. Detail 1 sheet 12: The bench shown are to comply with Accessible required complying to the ANSI 117. Provide drawings that illustrate the bench complying with this requirement.
2. Please resubmit.
01/09/2025 Commercial Electrical REQUIRES RESUBMIT Permit Review TC-COM-1224-02378 (950 N TUCSON BL TUCSON, AZ 85716)
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received.
Code reference, 2018 International Building Code (IBC), 2017 National Electrical Code (NEC).

1. Show or Note that all applicable electrical work shall comply with, Corrosive Environment – NEC 680.14
2. Provide GFCI protection in compliance with, GFCI Protection – NEC 680.21(C)
3. Verify WIRING note G on sheet E-002. Note shows #10 AWG conductor as minimum size for both conditions.

Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov
01/02/2025 Fire New Construction REQUIRES RESUBMIT Per the 2018 International Fire Code Section 3104.2 Flame propagation performance test ( Flame Certificate). Provide flame spread certification for the proposed materials to be used in the project.
If you have additional questions please contact me at Sal.erivezjr@tucsonaz.gov
01/10/2025 Outdoor Lighting REQUIRES RESUBMIT Outdoor Lighting Review TC-COM-1224-02378 (950 N TUCSON BL TUCSON, AZ 85716)
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received.
Code reference, 2018 International Building Code (IBC), 2017 National Electrical Code (NEC), 2012 Outdoor Lighting Code (OLC).

Outdoor Lighting Review:
1. Provide an outdoor lighting plan that meets the requirements of OLC 104.2. Show/locate the different light sources on your site plan. Number the light fixtures on your table and use the same number on your site plan
2. Provide a Special Inspection Certificate as required by OLC 106.2.
3. Show compliance with City of Tucson Outdoor Lighting Code with an approved lighting calculation in accordance with OLC 3.1.2. Include all exterior fixtures on the property in the calculations. Show unshielded fixtures with a maximum of 3,000 lumens, OLC 401.4. Show lamps with a maximum of 3500K color temperature, OLC 402.1.
4. Show compliance to total outdoor light output per 2012 City of Tucson/Pima County Outdoor Lighting Code section 401.2. Total outdoor light output shall not exceed the lumen limits listed in Table 401.1. 4. E1.1 – Lighting Code section 104.2.2.
5. Submit catalogue or specification sheets of the proposed light fixture illustrating the type of fixture they are whether full cut-off or unshielded.


Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov
01/31/2025 Site Engineering REQUIRES RESUBMIT TC-COM-1224-02378
950 N TUCSON BL

Site engineering comments are as follows:
1. See Zoning comment regarding the requirement for a development package. Refer to UDC Article 3.3.3.G.2.c.
Ryan Insalaco – ryan.insalaco@tucsonaz.gov
01/13/2025 Site Zoning REQUIRES RESUBMIT FROM: PDSD Zoning Review

PROJECT: TC-COM-1224-02378
950 N TUCSON BL. – R-2
Fabric shade canopy, pump equipment building, wall / metal fence (1st Review)

TRANSMITTAL DATE: January 13, 2025

Resubmit revised drawings detailed response letter, which states how all Zoning Review Section comments were addressed.

This site is located in the R-2 zone (UDC 4.7.9). Parks and Recreation is a permitted use in this zone (Table 4.8-2), subject to Use Specific Standards 4.9.13.B & C.

1. Per UDC Article 3.3.3.G.2.c A site plan (Development Package) is required for the following types of development: Existing development undergoing a change of use, building structure additions, and/or a reconfiguration of an area outside a building. A development package (DP) meeting the requirements of the Checklist for Minor Changes to Commercial/Industrial Sites is required to be submitted and approved. The DP is a separate submittal from the building plans. The checklist can be found at: https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/permits/minor_changes_to_commercial_industrial_sites_.pdf.

If you have any questions about this transmittal, please contact Zone1.desk@tucsonaz.gov.
12/27/2024 PDSD Application Completeness Express REVIEW COMPLETED