Permit Number: TC-COM-1224-02368
Parcel: 11619201C

Address:
2 N FREEWAY

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.2

Permit Number - TC-COM-1224-02368
Review Name: COMMERCIAL REVIEW - FULL v.2
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
02/10/2025 Commercial Building APPROVED Structural(S) Reviewer
Madeline Nelson
mnelson@safebuilt.com
Approved
Reason:
Date Completed : 2/8/2025 6:55:59 PM


Building(B) Reviewer
Keith Miller
kmiller@safebuilt.com
Approved
Reason:
Date Completed : 2/6/2025 9:59:20 AM
The plans are approved. Subject to the field inspector’s approval.
The completed Special Inspection Intermediate Certificate is to be submitted.
02/10/2025 Commercial Electrical APPROVED Electrical(E) Reviewer
Ron Ross
rross@safebuilt.com
Approved with Comments
Reason:
Date Completed : 2/5/2025 3:45:29 PM
02/10/2025 Outdoor Lighting APPROVED Electrical(E) Reviewer
Ron Ross
rross@safebuilt.com
Approved with Comments
Reason:
Date Completed : 2/5/2025 3:45:29 PM
02/20/2025 Bldg Permits - Post Review Express PENDING ASSIGNMENT
02/10/2025 Commercial Plumbing REQUIRES RESUBMIT Plumbing(P) Reviewer
Perry Hendershott
phendershott@safebuilt.com
Denied
Reason:
Date Completed : 2/6/2025 11:35:44 PM
Second Plumbing Review: Comment 5 Remains
Resolved-1). Plan Page A1.7: Missing Roof Drainage Method. Add roof drainage method with calculations. -2018 IPC
1101.2, 1106.1, 1106.2, 1106.3, 1106.6, 1108
Resolved-2). Plan Page A1.7: Missing location of adjacent secondary scuppers. Add adjacent secondary scuppers. -
2018 IPC 1106.5. 1108
Resolved-3). Plan page P1.1: Roof drain calc table missing conductor information. Add conductor information to roof
drainage calc table. -2018 IPC 1106.3
Resolved-4). Plan Page P1.1: Missing location of adjacent secondary scuppers. Add adjacent secondary scuppers. -
2018 IPC 1106.5. 1108
UNRESOLVED-5). Plan page P1.1.1 detail 2: add note for indirect waste piping that exceeds distances listed in -2018 IPC
802.3 will need to be trapped.
Resolved-6). Plan page P1.3: Water system detail is missing backflow protection for the H201 Oven water connection. Add
backflow protection for the H201 Oven water connection. -2018 IPC 608.3
Resolved-7). Plan pages P1.1.1 & P1.2: Grease laden waste needs to discharge to the grease system. The H201 Oven floor
sink needs to connect to the grease system, -2018 IPC 1003.1
02/20/2025 Site Engineering REQUIRES RESUBMIT See zoning comment

Ryan Insalaco – ryan.insalaco@tucsonaz.gov
02/20/2025 Site Zoning REQUIRES RESUBMIT FROM: Ramiro Olivarez
PDSD Zoning Review Section

PROJECT: TC-COM-1224-02368 – Commercial Building (ref. TD-DEV-0723-00337)
2 N FREEWAY – I-1| C-3
This site is zoned I-1 and C-3. Retail Use Group – General Merchandise Sales (Fuel Station) is a permitted use in these zones. (1st Review)

TRANSMITTAL DATE: February 20, 2025

COMMENTS: Resubmit revised drawings along with a detailed response letter, which states how all Zoning Review Section comments were addressed.

1. Comment: Although the plan appears to match, final Site Zoning approval of this plan cannot occur until development package, TD-DEV-0723-00337, is approved. Once approved, please resubmit the building permit. Ensure the building permit documents match the approved development package if any changes to the DP are made.

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Approval of TD-DEV-0723-00337 and resubmittal of revised plans.
If you have any questions about this transmittal, please contact Ramiro Olivarez at Ramiro.Olivarez@tucsonaz.gov
02/05/2025 PDSD Application Completeness Express REVIEW COMPLETED