Review Date Reviewer's Name Type of Review Description Status Comments
12/20/2024 Site Engineering NOT REQUIRED
12/20/2024 Bldg Permits - Post Review Express PENDING ASSIGNMENT
12/16/2024 Commercial Plumbing REQUIRES RESUBMIT 1. Provide calculations showing how the water service piping has been sized. Reference: Section 603.1, IPC 2018.
2. Provide the specifications for the type of Niron polypropylene pipe to be used, including the standard dimension ratio (SDR) and the ASTM standard to which it conforms. Reference: Section 605.3, IPC 2018.
3. Specify the type, conductivity, and thickness of the proposed pipe insulation for the above ground and the buried pipe. Reference: Sections C403.11.3 and C404.4, IECC 2018.