Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL PDSD SIMPLE REVIEW v.1
Permit Number - TC-COM-1224-02349
Review Name: COMMERCIAL PDSD SIMPLE REVIEW v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 12/20/2024 | Site Engineering | NOT REQUIRED | |||
| 12/20/2024 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 12/16/2024 | Commercial Plumbing | REQUIRES RESUBMIT | 1. Provide calculations showing how the water service piping has been sized. Reference: Section 603.1, IPC 2018. 2. Provide the specifications for the type of Niron polypropylene pipe to be used, including the standard dimension ratio (SDR) and the ASTM standard to which it conforms. Reference: Section 605.3, IPC 2018. 3. Specify the type, conductivity, and thickness of the proposed pipe insulation for the above ground and the buried pipe. Reference: Sections C403.11.3 and C404.4, IECC 2018. |
||
| 12/15/2024 | PDSD Application Completeness Express | REVIEW COMPLETED |