Permit Number: TC-COM-1224-02337
Parcel: 11621017A

Review Status: Requires Resubmit

Review Details: COMMERCIAL PDSD SIMPLE REVIEW v.1

Permit Number - TC-COM-1224-02337
Review Name: COMMERCIAL PDSD SIMPLE REVIEW v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
12/17/2024 Bldg Permits - Post Review Express PENDING ASSIGNMENT
12/17/2024 Commercial Electrical REQUIRES RESUBMIT Please address the electrical comments and provide a written response.

1 Please provide a detailed description of the scope of electrical work.

2 Provide complete electrical plans including design and calculations performed and sealed by a registrant registered in the State of Arizona.

Ref; 2018 IBC section 107.2.1, 2017 NEC, City of Tucson Commercial Plan Submittal Requirements.
12/16/2024 Commercial Mechanical REQUIRES RESUBMIT 1. Clarify the proposed cooling capacity for each air conditioner system, including the SEER2 for each system, and the heating capacity. The activity description calls out a 2-ton AC but the submitted condensing unit specifications are for a 4-ton AC. Reference: Section R103.2, IECC 2018.
2. The submitted condensing unit specification (GLXS4BA4810A) has a cooling capacity that is much greater than justified by the cooling load calculations. Sections R302.2, R403.7, and R503.1.2, IECC 2018 as amended by the City of Tucson.
3. Current Federal Regulations require residential split system air conditioners with a capacity of less than 45 MBH to have a minimum SEER2 of 14.3 (SEER 15). Verify that the proposed split system has a SEER2 that is at least 14.3.
4. The submittal does not describe the furnace section of the system. Is it existing or new? If it is new, is the gas load of the new unit equal to or less than the gas load of the existing furnace? Reference: Section 107.2.1, IBC 2018.
12/16/2024 Commercial Structural REQUIRES RESUBMIT Please submit your revised documents and provide a letter with a written response letter addressing each of the comments indicating how the Building Review comments were resolved. Additionally, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed.
1. Please amend the plans to provide a detailed description of the work in this permit’s scope. IBC 105.2
2. Please amend the plans to provide a list of the year and name of the adopted applicable codes from the adopting ordinance. IBC 107.2.1
3. It appears this project includes replacing existing evaporative coolers with new roof top AC units (RTU). Please provide an evaluation from an Arizona licensed design professional to indicate the existing roof structure can support the new RTU to include calculations, plans/details for the support of such equipment as needed. IBC 107.2.1 Alternatively, provide the weight of existing Evaporative Cooler to be removed and a comparison to the new RTU’s weight. If the new RTU weighs less than the existing, removed RTU all is good
a. Additionally, please provide drawing or manufacturer’s cut sheet for sheet metal stand.
Please contact me if you have any questions about these comments.
Mark Masek
Plans Examiner – Building Safety
Planning and Development Services | City of Tucson
main 520.837.4994
email mark.masek@tucsonaz.gov
12/13/2024 PDSD Application Completeness Express REVIEW COMPLETED