Review Status: Requires Resubmit
Review Details: COMMERCIAL REVIEW - LIMITED v.1
Permit Number - TC-COM-1224-02334
Review Name: COMMERCIAL REVIEW - LIMITED v.1
Review Status: Requires Resubmit
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
01/10/2025 | Commercial Structural | APPROVED | |||
01/09/2025 | Outdoor Lighting | NOT REQUIRED | |||
01/09/2025 | Commercial Electrical | REQUIRES RESUBMIT | Commercial Electrical Review TC-COM-1224-02334 (2020 W PRINCE RD Unit:UNIT 110 TUCSON, AZ 85705) Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received. Code reference, 2018 International Building Code (IBC), 2017 National Electrical Code (NEC). 1. Provide an electrical riser diagram, 2017 NEC 230.9. Provide a complete line diagram showing the connection from the service entrance to the panels, NEC 110.2, 2018 IBC 107.1. 2. Clarify and update the panel schedules. Panels MDPS1 and MDPS2 ‘REMARKS:” show a note “(**) Denotes Existing Lode – No Changes But Included in Project”. The panel schedules only show 2 circuits with this notation. Are all the other circuits new? 3. Provide electrical load calculations, for the Main Service Entrance to verify the existing Service Entrance can support the additional loads, Per NEC 220.40. Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov |
||
01/09/2025 | Commercial Mechanical | REQUIRES RESUBMIT | Provide heating and cooling load calculations to justify the heating/cooling capacities of the specified HVAC units. Reference: Sections C403.1.1 and C502.2.3, IECC 2018. | ||
01/10/2025 | Site Engineering | REQUIRES RESUBMIT | see zoning comments | ||
01/10/2025 | Site Zoning | REQUIRES RESUBMIT | ZONING REVIEW TRANSMITTAL FROM: PDSD Zoning Review PROJECT: TC-COM-1224-02334 2020 W PRINCE RD. – I-1 2-story modular office system ( 1st Review) TRANSMITTAL: January 10, 2025 This site is located in the I-1 zone (4.7.29). 1. As the proposed 2-story modular office system is adding square footage to the site a commercial site plan (development package) is required. UDC Article 3.3.3.G.2.c A site plan (Development Package) is required for the following types of development: Existing development undergoing a change of use, building structure additions, and/or a reconfiguration of an area outside a building. A development package (DP) meeting the requirements of Administrative Manual (AM) 2-06 must be submitted and approved prior to approval of this building plan. The Administrative Manual can be found at: https://www.tucsonaz.gov/Departments/Planning-Development-Services/Codes-and-Plans/Zoning-Code#section-1. 2. It appears that this permit is for the same 2-story modular office system as TC-COM-0724-01342. If this is the case than one or the other permit will need to be with drawn. If you have any questions about this transmittal, please contact Zone1.desk@tucsonaz.gov. |
||
01/10/2025 | Fire New Construction | REVIEW COMPLETED | |||
12/17/2024 | PDSD Application Completeness | REVIEW COMPLETED |