Permit Number: TC-COM-1224-02333
Parcel: 121093670

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-1224-02333
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
01/09/2025 Water - PDSD APPROVED
01/13/2025 Bldg Permits - Post Review Express PENDING ASSIGNMENT
12/23/2024 Commercial Building REQUIRES RESUBMIT Structural(S) Reviewer
Kimiyoshi Shimabukuro
kshimabukuro@safebuilt.com
Denied
Reason:
Date Completed : 12/23/2024 8:41:06 AM
1. Provide Special Inspections Intermediate Certificate
◦ A Special Inspections Intermediate Certificate must be submitted and reviewed prior to issuance of this permit. Provide signed/dated certificate: S1.0 note R.1 states the employment of special inspectors to provide inspection and testing during construction (S1.1).
◦ You may obtain the form at the following link:
◦ https://www.tucsonaz.gov/files/sharedassets/public/v/1/city-services/planning-developmentservices/documents/special_inspection_certificate.pdf
◦ The Condition is added to the permit and then satisfied upon approval of the form.
2. Geotechnical report part 6.4 pavement design shows minimum compressive strength of 4,000 PSI concrete slab at 28 days at trash pickup areas but detail 7/A503 shows design strength of 3,000 PSI.
3. Geotechnical report Part 6.2.4 indicates using 2012 International Building Code. City of Tucson adopts 2018 IBC.




Building(B) Reviewer
Kimiyoshi Shimabukuro
kshimabukuro@safebuilt.com
Denied
Reason:
Date Completed : 12/23/2024 8:42:18 AM
1. Cover sheet – 32 sheets listed in sheet list but 34 pages submitted. Clarify scope of work (2018 IBC section 107.2.1).
2. A100 – Enlarged site plan – key notes refer to Civil drawings for additional information, but Civil sheets are missing.
3. A202 – EIFS system identified but missing special inspections per 2018 IBC section 1705.16.
4. Geotechnical report part 8.0 states the ground surface should slope away from the buildings at a minimum 5% slope for at least 10 feet away from the buildings, but this is not shown in A100 architectural site plan.
12/23/2024 Commercial Electrical REQUIRES RESUBMIT Electrical(E) Reviewer
Kimiyoshi Shimabukuro
kshimabukuro@safebuilt.com
Denied
Reason:
Date Completed : 12/23/2024 8:41:59 AM
1. E0.1 – Dimensions and detail of concrete pad for transformer is missing.
2. E1.0 – RTU AC/2 missing GFCI receptacle. 2017 NEC section 210.8(B)(3)
3. E1.1 – Show compliance to total outdoor light output per 2012 City of Tucson/Pima County Outdoor Lighting Code section 401.2. Total outdoor light output shall not exceed the lumen limits listed in Table 401.1.
4. E1.1 – Lighting Code section 104.2.2 – The plan submission shall contain a note indicating whether special inspection is required in accordance with Section 106.
12/23/2024 Commercial Mechanical REQUIRES RESUBMIT Mechanical(M) Reviewer
Kimiyoshi Shimabukuro
kshimabukuro@safebuilt.com
Denied
Reason:
Date Completed : 12/23/2024 8:41:42 AM
1. M1.0 shows contradicting natural gas and electrical source AC rooftop units. Clarify which is being proposed. (2018 IMC section 106.3.1) P1.0 shows gas and E2.0 shows AC-1, 2, and 3 using electricity.
12/23/2024 Commercial Plumbing REQUIRES RESUBMIT Plumbing(P) Reviewer
Kimiyoshi Shimabukuro
kshimabukuro@safebuilt.com
Denied
Reason:
Date Completed : 12/23/2024 8:41:22 AM
1. A100 – General notes B states to place grease interceptor on-site as required by jurisdiction which is undefined scope (2018 IPC section 106.3.1). Provide grease interceptor design plan per City of Tucson amendments to the 2018
International Plumbing Code section 1003.3 Grease interceptors. P1.0 shows GT1 hydromechanical grease interceptors which section 1003.3 allows up to (4) or fewer fixtures. Explain
01/08/2025 Outdoor Lighting REQUIRES RESUBMIT Outdoor Lighting Review TC-COM-1224-02333 (2121 N CRAYCROFT RD Unit:BLDG 4 TUCSON, AZ 85712)
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received.
Code reference, 2018 International Building Code (IBC), 2017 National Electrical Code (NEC), 2012 Outdoor Lighting Code (OLC).

Outdoor Lighting

1. Show compliance to total outdoor light output per 2012 City of Tucson/Pima County Outdoor Lighting Code section 401.2. Total outdoor light output shall not exceed the lumen limits listed in Table 401.1. 4. E1.1 – Lighting Code section 104.2.2.
2. Update Allowable Lumens/Acre, and compliance calculations, with a Total (full cut-off plus unshielded) 175,000 and Limit on unshielded component 11,000.

Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov
01/09/2025 Site Engineering REQUIRES RESUBMIT TC-COM-1224-02333
2121 N CRAYCROFT RD

Site engineering comments are as follows:
1. TC-COM-1224-02333 requires a revision to the building 4 section of the tentative plat, (DP17-0182). The site plan on the building permit does not match the building 4 footprint on the development package. The building 4 revision to the plat must be approved before this building permit can be formally reviewed and approved.
Ryan Insalaco – ryan.insalaco@tucsonaz.gov
01/13/2025 Site Zoning REQUIRES RESUBMIT FROM: PDSD Zoning Review Section

PROJECT: TC-COM-1224-02333 - DP17-0182
2121 N. CRAYCROFT RD. - OCR-1
Food Service (1st Review)

TRANSMITTAL DATE: ‎January 13, 2025

COMMENTS: Resubmit revised drawings along with a detailed response letter, which states how all Zoning Review Section comments were addressed.

This site is located in the C-2 zone (UDC 4.7.21). Food Service is a permitted use in the zone (UDC Table 4.8-4).

1. Zoning has reviewed this building plan for compliance with Development Package (DP) DP17-0182, and although the plans appear to match, until the DP revision is approved by all review agencies Zoning cannot approve this building permit.

If you have any questions about this transmittal, please contact Zone1.desk@tucsonaz.gov.
01/06/2025 Fire New Construction REVIEW COMPLETED
12/17/2024 PDSD Application Completeness Express REVIEW COMPLETED