Permit Number: TC-COM-1224-02331
Parcel: 11451206B

Review Status: Requires Resubmit

Review Details: COMMERCIAL POOLS v.1

Permit Number - TC-COM-1224-02331
Review Name: COMMERCIAL POOLS v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
01/02/2025 Bldg Permits - Post Review Express PENDING ASSIGNMENT
12/23/2024 Commercial Building REQUIRES RESUBMIT Structural(S) Reviewer
Kimiyoshi Shimabukuro
kshimabukuro@safebuilt.com
Denied
Reason:
Date Completed : 12/21/2024 6:55:19 PM
1. Provide Special Inspections Intermediate Certificate
◦ A Special Inspections Intermediate Certificate must be submitted and reviewed prior to issuance of this permit. Provide signed/dated certificate: SP-001 mentions inspection of record. You may obtain the form at the following link:
◦ https://www.tucsonaz.gov/files/sharedassets/public/v/1/city-services/planning-developmentservices/documents/special_inspection_certificate.pdf
◦ The Condition is added to the permit and then satisfied upon approval of the form.



Building(B) Reviewer
Kimiyoshi Shimabukuro
kshimabukuro@safebuilt.com
Denied
Reason:
Date Completed : 12/21/2024 6:58:58 PM
1. SP-101 – Show location and details of swimming pool access gates per 2018 ISPSC section 305.3 that is equipped to accommodate a locking device. Pedestrian access gate shall open outward away from the pool or spa, shall be selfclosing and shall have a self-latching device.
2. SP-101 – Provide slope and drain direction per 2018 ISPSC section 306.5.
3. SP-101 – Locate hose bibbs per 2018 ISPS section 306.9.1.
4. Provide building code information such as area (SF), occupancy group classification and total occupancy load per
2018 IBC chapters 3 section 302 and chapter 10 section 1004.
5. Provide means of egress plan per 2018 IBC chapter 10.
6. Missing submission of A3.0, I-15, L-16 and L-17 those mentioned in sheet index.
7. SP-101 - DE16 and DE17 state to see architectural sheets but they are missing in submission.
8. SP-111 – 2018 ISPSC section 302.5 states water supplies for pools and spas shall be protected against backflow.
9. SP-503 – Main drain missing key note. 2018 ISPSC section 310 to provide suction entrapment avoidance for pools and spas accordance with APSP 7.
10. General – In climate subject to freezing temperatures, outdoor pool and spa shells and appurtenances, piping, filter systems, pumps and motors, and other components shall be designed and constructed to provide from damage from
freezing.
11. Missing minimum plumbing facilities per 2018 IPC section 403. Show minimum and provided plumbing fixture calculations. Water closets, lavatories, drinking fountain and others. Pools description listed in assembly classification.
01/02/2025 Site Zoning REQUIRES RESUBMIT PDSD TRANSMITTAL

FROM:
Fernando García
Planning & Development Services Department – Zoning Review Section

PROJECT:
TC-COM-1224-02331 (Commercial Pool)
2945 N Bear Canyon Rd, Tucson, AZ 85749
Building Plan Review (1st Review)

TRANSMITTAL DATE: December 23, 2024

This site is located in the R-3 zone (UDC 4.7.12). Per UDC Table 4.8-2, multifamily development is a permitted use subject to use-specific standard 4.9.7.B.6.

1. (Comment) The submitted plans show a different pool design and inclusion of an equipment building that is not shown on the approved development packages for this project (DP21-0174 and DP22-0172).

A revision to the development packages will be required before this permit can be approved.

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revisions to DP21-0174 and DP22-0172. Revised plans, with a comment response letter that indicates the response to each comment.

If you have any questions about this transmittal, please contact Fernando L. Garcia at fernando.garcia2@tucsonaz.gov.
12/14/2024 PDSD Application Completeness Express REVIEW COMPLETED