Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL REVIEW - FULL v.1
Permit Number - TC-COM-1224-02319
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
01/07/2025 | Commercial Mechanical | APPROVED | |||
01/06/2025 | Water - PDSD | APPROVED | |||
01/10/2025 | Bldg Permits - Post Review | PENDING ASSIGNMENT | |||
01/07/2025 | Commercial Building | REQUIRES RESUBMIT | Please submit your revised documents and provide a letter with a written response letter addressing each of the comments indicating how the Review comments were resolved. Building Review 1. Sheet T1.0: Please update the list of Current Adopted Codes to include the 2012 City of Tucson/Pima County Outdoor Lighting Code IBC 107.2.1 2. Sheet T1.0: Please update the Sheet Index, or plan set sheets to provide list that includes all the drawing sheets in this permit’s scope. IBC 107.2.1 For example, Listed in Sheet index, but not included in plan set Sheets C1-C5, D2.0, S1.7, S1.8, and Not Listed in Sheet index, but included in plan set Sheet D1.1 3. Sheet T1.0: Please change the signage to be by a separate permit. IBC 107.2.1 4. Sheet T1.0: Please update Code Analysis to indicate the occupancy classification to identify the mixed occupancy methodology as either nonseparated, separated, or a stated combination of types. IBC 508.1 or provide and name the method used to create separate buildings and show on the floor plan. IBC 107.2.1 A. Related to the above comment: Please amend the plans to show the method of separation between the proposed S-1 and the balance of the existing occupancies, in particular the existing A-2’s at the East corner of the development. IBC Table 508.4 5. Please amend the plans to show and label the set sack or Fire Separation Distance (FSD) from Building ‘A’ to the property line. IBC 107.2.6 6.Please amend plans as it appears the exterior property side wall should be rated at Building ‘A’. per IBC Table 602. It looks like the distance is 1’-11”,this will require a rated exterior wall based on IBC Table 602 and constructed in accordance with IBC 705 Likely including a parapet. 7. Please amend the plans to list the required special inspections on the cover sheet. IBC 107.2.1 8. Please amend the Statement of Special Inspections for Concrete Construction, since it is a copy of the table from the code, to identify which areas are required for this project. For example, another column could be added to the table with each required row of the table marked Y or N. (Further, Is Row 10. INSPECT ERECTION OF PRECAST CONCRETE MEMBERS a special inspection component required for this project?) Treat as a typical note, and please provide project specific Statement of Special Inspections for this project. 9. Please list the required special inspections on the Title Sheet. IBC 107.2.1 10. Soils Special Inspection: Please provide the City of Tucson Special Inspection Certificate(s) with Parts A and B completed with the next submittal. IBC 107.1 SI form link: https://www.tucsonaz.gov/files/sharedassets/public/v/1/city-services/planning-development-services/documents/special_inspection_certificate.pdf Please contact me if you have any questions about these comments. Mark Masek Plans Examiner – Building Safety Planning and Development Services | City of Tucson main 520.837.4994 email mark.masek@tucsonaz.gov |
||
01/07/2025 | Commercial Electrical | REQUIRES RESUBMIT | Please submit your revised documents and provide a letter with a written response letter addressing each of the comments indicating how the Review comments were resolved. Electrical Review 1. Sheet E0.2 : Please amend the Exterior Luminaire Schedule (and cutsheets on sheet E0.5) to show a maximum color temperature of 3500K for exterior light fixtures. Outdoor Lighting Code 402.1 Rated Color Temperature. The rated color temperature of light sources (lamps and fixtures) shall not exceed 3500K. Treat as a typical note. 2. Sheet E0.4: Provide complete compliance with the 2012 City of Tucson Outdoor Lighting Code (OLC). See section 104 for exterior lighting plan submittal requirements. Provide plans and evidence on the plans that the proposed exterior lighting fully complies with the Outdoor Lighting Code. See section 104 for plan submittal requirements. Change of use. Whenever the use of any existing building, structure, or premises is changed to a new use, all outdoor lighting shall be reviewed and brought into compliance with this code before the new use commences. (OLC)102.5 3. Provide site lighting plans with the following information on the plans; A. Full compliance with sections 104.2.1(1), (2), (3). B. See table 401.1, Include parcel size, lighting area and option, and indicate this information in the lighting site plan. 3 402.1 (light source color temperature requirements, 3500K), shielding requirements, etc . C. Provide calcs for total lumens allowed and total lumens proposed per acre for Full Cut Off and Unshielded per table 401.1. Must include existing to remain lighting. D. Indicate whether or not a special inspection is required per sec. 104.2.2, and 106.2. E. Specify any exceptions used. F. Provide Curfew lighting controls If applicable Per section 403. Ref; 2017 NEC, 2012 Tucson/Pima County Outdoor Lighting Code (OLC), 2018 IBC sec 107.2.1. 2018 IECC. Ref 2018 IBC section 107.2.1, 2017 NEC, 2012 City of Tucson Outdoor Lighting Code (OLC). Link to 2012 Outdoor Lighting Code below: https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/building-code/2012_outdoor_lighting_code_.pdf Please contact me if you have any questions about these comments. Mark Masek Plans Examiner – Building Safety Planning and Development Services | City of Tucson main 520.837.4994 email mark.masek@tucsonaz.gov |
||
01/06/2025 | Commercial Plumbing | REQUIRES RESUBMIT | Clarify the location of the hub drain for water heater WH-1. Indirect waste receptors shall not be installed in plenums, crawl spaces, attics, interstitial spaces above ceilings and below floors. Indirect waste receptors shall have ready access. Reference: Section 802.4, IPC 2018. | ||
01/10/2025 | Fire New Construction | REQUIRES RESUBMIT | -Resolve all building comments. -Sheet T1.0, Deferred submittals. You have a note stated building will be tested for ERRC. This building is not required to be tested, however, you can have it tested if you would like. Either keep the note and follow through with testing or remove the note. john.vincent@tucsonaz.gov 5203495581 |
||
01/07/2025 | Site Engineering | REQUIRES RESUBMIT | 1. The associated development package TD-DEV-1124-00308 must be approved before this building permit can be approved. 2. A separate building permit is required for each building. One permit cannot be issued for multiple buildings. Mike Ortiz michael.ortiz@tucsonaz.gov |
||
01/10/2025 | Site Zoning | REQUIRES RESUBMIT | FROM: PDSD Zoning Review Section PROJECT: TC-COM-1224-02319 - TD-DEV-1124-00308 1104 S CRAYCROFT RD. - C-2 Personal Storage (1st Review) TRANSMITTAL DATE: January 10, 2025 COMMENTS: Resubmit revised drawings along with a detailed response letter, which states how all Zoning Review Section comments were addressed. This site is located in the C-2 zone (UDC 4.7.21). Personal Storage is a permitted use in the zone (UDC Table 4.8-4), subject to Use Specific Standards 4.9.10.C.3 & .6. 1. Zoning has reviewed this building plan for compliance with Development Package (DP) TD-DEV-1124-00308. The following comments shall be addressed prior to approval of the building plans. 2. The site plan provided in the building set does not match the submitted DP, i.e. area directly north of the existing building. 3. As the DP does not provide building heights within the footprints of the building as required per AM 2-06 Zoning cannot verify if the plans match. 4. Until the DP is approved by all review agencies Zoning cannot approve the building plans. If you have any questions about this transmittal, please contact Zone1.desk@tucsonaz.gov. |
||
12/16/2024 | PDSD Application Completeness | REVIEW COMPLETED |