Permit Number: TC-COM-1224-02311
Parcel: 106041010

Address:
320 E YAVAPAI RD

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - LIMITED v.1

Permit Number - TC-COM-1224-02311
Review Name: COMMERCIAL REVIEW - LIMITED v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
12/20/2024 Commercial Building NOT REQUIRED
12/30/2024 Site Zoning NOT REQUIRED
12/30/2024 Bldg Permits - Post Review Express PENDING ASSIGNMENT
12/22/2024 Commercial Electrical REQUIRES RESUBMIT Please submit your Electrical drawings done by a State licensed Electrical Engineer. Show your panel schedule as well as you electrical load calculation. Please re-submit.
12/22/2024 Outdoor Lighting REQUIRES RESUBMIT ACTIVITY NO. TC-COM-1224-02311
ADDRESS/PARCEL: (320 E YAVAPAI RD TUCSON, AZ 85705)
Submit your revised drawings along with a detailed response letter, which states how all Building Review Section comments were addressed. The submitted documents were incomplete and a thorough plan review could not be performed. Please be aware, new comments may arise with the next review. Review will not proceed without the response letter.
COMMENTS:
1. The submitted Apartment Plan contains 2 parcels and 2 addresses. Two building permits are required. Being that this permit is using the address 320 E Yavapai Rd, you may continue processing this permit for this address (the City will continue reviewing this set of submittal for this address by crossing out the structure addressed 332 E Yavapai Rd).
2. Please apply for another building permit for the address 332 E Yavapai Rd. Ensure to submit only the parcel and structure for this second address.
3. Per section 401.2.1 of the City of Tucson/Pima County Outdoor Lighting Code, One hundred percent of the lumens from outdoor light fixtures installed on grade, on poles, and installed on the top or sides of buildings of other structures shall be submitted with your drawings. Please be clear in illustrating this on your drawing by creating a table.
a. Per section 402.1 of the Outdoor Lighting Code, The rated color temperature of light sources (lamps and fixtures) shall not exceed 3500K
b. On the table indicate the type of light, its lumens, its Kelvin rated color temperature, now many of that light type and the total lumens for that light type.
c. At the bottom of that table, indicate/show the total lumens for separately for the shielded and unshielded.
d. Total outdoor light output shall not exceed the lumen limits listed in Table 401.1. In the table, “total” means the sum of shielded and unshielded light.
4. The submitted catalogue cut of the proposed light fixture is vague.
a. Please select the color temperature that you are proposing.
b. Please select the lumen output that you are proposing.
c. The catalogue cut indicates fixture is dark sky compliant when full cutoff visor is installed, it further say not included. Please select and specify that this light fixture is to be dark sky compliant by including the full cutoff visor.
d. The image of the light fixture does not show the visor. Please submit the light fixture with the full cutoff visor within the light fixture image.
5. As part of your submittal, indicate the Lighting Area the parcel belongs.
6. Provide your lumens calculation as to the shielded/full cutoff and unshielded allowed for that parcel. (NOTE: Please be mindful of Table 401.1 of the Outdoor Lighting Code is setup. The first row under each type of lighting configuration, indicates the Total (full cut-off plus unshielded. The second row indicates the limit of the unshielded component. Therefore when calculating your lumens allowed subtract the unshielded lumens from the first row in order to calculate the lumens accurately.)
7. Please don’t forget to show/locate the different light sources on your apartment plan.
8. Please peruse the following as part of your requirement.
401.3 Shielding requirements. All light fixtures that are required to be shielded shall be installed in such a
manner that the shielding is effective and permanent.
401.3.1 Light trespass. Light fixtures on the residential side of commercial property adjacent to
residential property shall be full cutoff and shall be installed not higher than 10 feet above grade at the
property line and no higher than a line rising 20 degrees above the 10 feet until 100 feet from the
property line, measured perpendicular to the lot line.
401.3.2 House Side Shields. Outdoor lighting fixtures closer to the lot line than the mounting height of
the fixture, measured perpendicular to the lot line, adjacent to residential areas, shall have internal
house-side shields.
401.3.3 Fixtures within 25 feet of residential lot lines. Residential and commercial luminaires shall
be full cutoff within 25 feet of adjacent residential property lines, measured perpendicular to the lot
line.
401.3.4 Flood and spot lamps. Flood or spot lamps shall be aimed no higher than 45 degrees to the
horizontal (half-way between straight down and straight to the side) when the source is visible from
any adjacent residential property.
9. Please resubmit.
12/15/2024 PDSD Application Completeness Express REVIEW COMPLETED