Permit Number: TC-COM-1224-02303
Parcel: 123160470

Review Status: Requires Resubmit

Review Details: COMMERCIAL PDSD SIMPLE REVIEW v.1

Permit Number - TC-COM-1224-02303
Review Name: COMMERCIAL PDSD SIMPLE REVIEW v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
12/17/2024 Site Engineering NOT REQUIRED
12/17/2024 Bldg Permits - Post Review Express PENDING ASSIGNMENT
12/10/2024 Commercial Electrical REQUIRES RESUBMIT Please address the electrical plan review comments and provide a written response.

1 Please provide complete electrical plans. Include;

a. Complete electrical line diagram.

b. Complete panel schedules for the new load centers.

c. Total load calculations for the electrical service associated with this project.

d. Show location of the new load centers.

e. Show all new branch circuits or feeders associated with the new load centers on the electrical floor plans.

REf; 2018 IBC section 107.2.1, 2017 NEC, City of Tucson Commercial Plan Submittal Requirements.