Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL REVIEW - LIMITED v.1
Permit Number - TC-COM-1224-02286
Review Name: COMMERCIAL REVIEW - LIMITED v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 12/19/2024 | Commercial Building | APPROVED | |||
| 12/19/2024 | Commercial Electrical | APPROVED | |||
| 12/26/2024 | Site Zoning | APPROVED | |||
| 12/19/2024 | Water - PDSD | APPROVED | |||
| 12/26/2024 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 12/19/2024 | Commercial Mechanical | REQUIRES RESUBMIT | 1. The induction range is a medium-duty cooking appliance. A Type I hood shall be installed over medium-duty cooking appliances. Reference: Sections 202 and 507.2, IMC 2018. 2. Show how ventilation of the kitchen will comply with the requirements of Section 403.2.1, exception 3, IMC 2018. Reference: Table 403.3.1.1, IMC 2018. |
||
| 12/19/2024 | Commercial Plumbing | REQUIRES RESUBMIT | Revise the hot water distribution plan so that the distance from the hot water source to the hot water termination for the public lavatory complies with the requirements of Section C404.5, IECC 2018. | ||
| 12/23/2024 | Fire New Construction | REVIEW COMPLETED | |||
| 12/11/2024 | PDSD Application Completeness Express | REVIEW COMPLETED | |||
| 12/24/2024 | Site Engineering | REVIEW COMPLETED |