12/19/2024 Commercial Building APPROVED
12/19/2024 Commercial Electrical APPROVED
12/26/2024 Site Zoning APPROVED
12/19/2024 Water - PDSD APPROVED
12/26/2024 Bldg Permits - Post Review Express PENDING ASSIGNMENT
12/19/2024 Commercial Mechanical REQUIRES RESUBMIT 1. The induction range is a medium-duty cooking appliance. A Type I hood shall be installed over medium-duty cooking appliances. Reference: Sections 202 and 507.2, IMC 2018.
2. Show how ventilation of the kitchen will comply with the requirements of Section 403.2.1, exception 3, IMC 2018. Reference: Table 403.3.1.1, IMC 2018.
12/19/2024 Commercial Plumbing REQUIRES RESUBMIT Revise the hot water distribution plan so that the distance from the hot water source to the hot water termination for the public lavatory complies with the requirements of Section C404.5, IECC 2018.
12/23/2024 Fire New Construction REVIEW COMPLETED
12/11/2024 PDSD Application Completeness Express REVIEW COMPLETED
12/24/2024 Site Engineering REVIEW COMPLETED