Review Status: Requires Resubmit
Review Details: COMMERCIAL REVIEW - LIMITED v.2
Permit Number - TC-COM-1224-02286
Review Name: COMMERCIAL REVIEW - LIMITED v.2
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/28/2025 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 01/28/2025 | Commercial Mechanical | REQUIRES RESUBMIT | The induction range has been replaced by a countertop cooker which does not require a hood. An existing exhaust grille appears to be located in the kitchen area but the exhaust air flowrate is not shown. The minimum exhaust rate shall be 0.70 CFM per square foot, using a minimum area of 100 square feet for each individual appliance (i.e., 70 CFM in this case). Reference: Section 507.1, exception 2 and 507.3, IMC 2018. [Initial comment: The induction range is a medium-duty cooking appliance. A Type I hood shall be installed over medium-duty cooking appliances. Reference: Sections 202 and 507.2, IMC 2018.] | ||
| 01/28/2025 | Commercial Plumbing | REQUIRES RESUBMIT | The hot water loop has been re-routed but the hot water source still does not appear to be within 24” of the lavatory. [Initial comment: Revise the hot water distribution plan so that the distance from the hot water source to the hot water termination for the public lavatory complies with the requirements of Section C404.5, IECC 2018. | ||
| 01/14/2025 | PDSD Application Completeness Express | REVIEW COMPLETED |