Permit Number: TC-COM-1224-02286
Parcel: 112054100

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - LIMITED v.2

Permit Number - TC-COM-1224-02286
Review Name: COMMERCIAL REVIEW - LIMITED v.2
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
01/28/2025 Bldg Permits - Post Review Express PENDING ASSIGNMENT
01/28/2025 Commercial Mechanical REQUIRES RESUBMIT The induction range has been replaced by a countertop cooker which does not require a hood. An existing exhaust grille appears to be located in the kitchen area but the exhaust air flowrate is not shown. The minimum exhaust rate shall be 0.70 CFM per square foot, using a minimum area of 100 square feet for each individual appliance (i.e., 70 CFM in this case). Reference: Section 507.1, exception 2 and 507.3, IMC 2018. [Initial comment: The induction range is a medium-duty cooking appliance. A Type I hood shall be installed over medium-duty cooking appliances. Reference: Sections 202 and 507.2, IMC 2018.]
01/28/2025 Commercial Plumbing REQUIRES RESUBMIT The hot water loop has been re-routed but the hot water source still does not appear to be within 24” of the lavatory. [Initial comment: Revise the hot water distribution plan so that the distance from the hot water source to the hot water termination for the public lavatory complies with the requirements of Section C404.5, IECC 2018.
01/14/2025 PDSD Application Completeness Express REVIEW COMPLETED