Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL REVIEW - FULL v.2
Permit Number - TC-COM-1224-02280
Review Name: COMMERCIAL REVIEW - FULL v.2
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 09/10/2025 | Site Zoning | APPROVED | Development Package (DP22-0071) and Special District (SD-0125-00003) approved | ||
| 09/09/2025 | Water - PDSD Standard | APPROVED | |||
| 09/10/2025 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 09/08/2025 | Commercial Building Standard | REQUIRES RESUBMIT | September 5, 2025 1st Review CMA, LLC. Attn: Chuck Meyer 1900 N. Fremont Avenue Tucson, Arizona 85719 Re: DOWNER OFFICE TENANT IMPROVEMENT City of Tucson Permit Number: TC-COM-1224-02280 Stantec Project Number: 185215066 Stantec File Number: TUC-25-088 Plan review for the above referenced project has been completed. This letter reflects comments to be addressed. PLEASE send all response to comments back to the City through the permit portal! Responses sent directly to Stantec will be ignored. Also, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed. Please cloud and delta all changes and provide a letter with a written response to each of the comments indicating the action taken. The scope of this review covers the architectural, structural, plumbing, mechanical, and electrical designs as they relate to the codes adopted by the jurisdiction. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions, and concerns before permit approval. Occupancy Group Construction Type Area (Square feet) Occupant Load Automatic Fire Sprinklers Fire Alarms B V-B 2,143 22 No No Separate Permits: None. Deferred Submittals: Type I hood. Special Inspections: Epoxy and expansion anchors. ARCHITECTURAL COMMENTS General 1. Please provide proof that this project has been submitted to the Pima County Health Department for permitting. Make sure to incorporate any of their comments into any future submittals. 2. Please provide City of Tucson special inspection certificate(s) with Parts A and B completed for epoxy and expansion anchors. Make sure that the owner or their legal representative signs the form. 3. Please remove the welding from the special inspections indicated on the cover. The structural design does not appear to require field welding. Sheet A1 1. The plans do not indicate a drinking fountain. Please provide and include in plumbing calculations on the cover sheet. [Ref. IPC 2018 Sec. 2902.1] 2. The plans do not indicate a service sink. Please provide and include in plumbing calculations on the cover sheet. [Ref. IPC 2018 Sec. 2902.1] 3. The proposed kitchen layout does not meet the minimum clearance requirements of 60” between cabinets, countertops, appliances, or walls within the kitchen work area for U-shaped kitchens. Please revise. [Ref. ICC A117.1-2009 Sec. 804.2.2] 4. The accessible bathroom at the hallway does not meet accessibility clearance requirements. The door swings within the clear floor space and fixture clearances, a 5’ turning radius does not appear to fit in the room, fixtures are not allowed within the water closet clearance. Please revise. [Ref. ICC A117.1-2009 Sec. 304 & 604] 5. Please provide the manufacturer’s specifications for the proposed kitchen equipment to help determine if kitchen hoods will be required for the proposed project. STRUCTURAL COMMENTS There are no comments. MECHANICAL COMMENTS There are no comments. PLUMBING COMMENTS There are no comments. ELECTRICAL COMMENTS There are no comments. Should you have any questions regarding the plan review comments, please contact the plan reviewer listed for the appropriate discipline. |
||
| 09/08/2025 | Commercial Electrical Standard | REQUIRES RESUBMIT | September 5, 2025 1st Review CMA, LLC. Attn: Chuck Meyer 1900 N. Fremont Avenue Tucson, Arizona 85719 Re: DOWNER OFFICE TENANT IMPROVEMENT City of Tucson Permit Number: TC-COM-1224-02280 Stantec Project Number: 185215066 Stantec File Number: TUC-25-088 Plan review for the above referenced project has been completed. This letter reflects comments to be addressed. PLEASE send all response to comments back to the City through the permit portal! Responses sent directly to Stantec will be ignored. Also, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed. Please cloud and delta all changes and provide a letter with a written response to each of the comments indicating the action taken. The scope of this review covers the architectural, structural, plumbing, mechanical, and electrical designs as they relate to the codes adopted by the jurisdiction. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions, and concerns before permit approval. Occupancy Group Construction Type Area (Square feet) Occupant Load Automatic Fire Sprinklers Fire Alarms B V-B 2,143 22 No No Separate Permits: None. Deferred Submittals: Type I hood. Special Inspections: Epoxy and expansion anchors. ARCHITECTURAL COMMENTS General 1. Please provide proof that this project has been submitted to the Pima County Health Department for permitting. Make sure to incorporate any of their comments into any future submittals. 2. Please provide City of Tucson special inspection certificate(s) with Parts A and B completed for epoxy and expansion anchors. Make sure that the owner or their legal representative signs the form. 3. Please remove the welding from the special inspections indicated on the cover. The structural design does not appear to require field welding. Sheet A1 1. The plans do not indicate a drinking fountain. Please provide and include in plumbing calculations on the cover sheet. [Ref. IPC 2018 Sec. 2902.1] 2. The plans do not indicate a service sink. Please provide and include in plumbing calculations on the cover sheet. [Ref. IPC 2018 Sec. 2902.1] 3. The proposed kitchen layout does not meet the minimum clearance requirements of 60” between cabinets, countertops, appliances, or walls within the kitchen work area for U-shaped kitchens. Please revise. [Ref. ICC A117.1-2009 Sec. 804.2.2] 4. The accessible bathroom at the hallway does not meet accessibility clearance requirements. The door swings within the clear floor space and fixture clearances, a 5’ turning radius does not appear to fit in the room, fixtures are not allowed within the water closet clearance. Please revise. [Ref. ICC A117.1-2009 Sec. 304 & 604] 5. Please provide the manufacturer’s specifications for the proposed kitchen equipment to help determine if kitchen hoods will be required for the proposed project. STRUCTURAL COMMENTS There are no comments. MECHANICAL COMMENTS There are no comments. PLUMBING COMMENTS There are no comments. ELECTRICAL COMMENTS There are no comments. Should you have any questions regarding the plan review comments, please contact the plan reviewer listed for the appropriate discipline. |
||
| 09/08/2025 | Commercial Mechanical Standard | REQUIRES RESUBMIT | September 5, 2025 1st Review CMA, LLC. Attn: Chuck Meyer 1900 N. Fremont Avenue Tucson, Arizona 85719 Re: DOWNER OFFICE TENANT IMPROVEMENT City of Tucson Permit Number: TC-COM-1224-02280 Stantec Project Number: 185215066 Stantec File Number: TUC-25-088 Plan review for the above referenced project has been completed. This letter reflects comments to be addressed. PLEASE send all response to comments back to the City through the permit portal! Responses sent directly to Stantec will be ignored. Also, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed. Please cloud and delta all changes and provide a letter with a written response to each of the comments indicating the action taken. The scope of this review covers the architectural, structural, plumbing, mechanical, and electrical designs as they relate to the codes adopted by the jurisdiction. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions, and concerns before permit approval. Occupancy Group Construction Type Area (Square feet) Occupant Load Automatic Fire Sprinklers Fire Alarms B V-B 2,143 22 No No Separate Permits: None. Deferred Submittals: Type I hood. Special Inspections: Epoxy and expansion anchors. ARCHITECTURAL COMMENTS General 1. Please provide proof that this project has been submitted to the Pima County Health Department for permitting. Make sure to incorporate any of their comments into any future submittals. 2. Please provide City of Tucson special inspection certificate(s) with Parts A and B completed for epoxy and expansion anchors. Make sure that the owner or their legal representative signs the form. 3. Please remove the welding from the special inspections indicated on the cover. The structural design does not appear to require field welding. Sheet A1 1. The plans do not indicate a drinking fountain. Please provide and include in plumbing calculations on the cover sheet. [Ref. IPC 2018 Sec. 2902.1] 2. The plans do not indicate a service sink. Please provide and include in plumbing calculations on the cover sheet. [Ref. IPC 2018 Sec. 2902.1] 3. The proposed kitchen layout does not meet the minimum clearance requirements of 60” between cabinets, countertops, appliances, or walls within the kitchen work area for U-shaped kitchens. Please revise. [Ref. ICC A117.1-2009 Sec. 804.2.2] 4. The accessible bathroom at the hallway does not meet accessibility clearance requirements. The door swings within the clear floor space and fixture clearances, a 5’ turning radius does not appear to fit in the room, fixtures are not allowed within the water closet clearance. Please revise. [Ref. ICC A117.1-2009 Sec. 304 & 604] 5. Please provide the manufacturer’s specifications for the proposed kitchen equipment to help determine if kitchen hoods will be required for the proposed project. STRUCTURAL COMMENTS There are no comments. MECHANICAL COMMENTS There are no comments. PLUMBING COMMENTS There are no comments. ELECTRICAL COMMENTS There are no comments. Should you have any questions regarding the plan review comments, please contact the plan reviewer listed for the appropriate discipline. |
||
| 09/08/2025 | Commercial Plumbing Standard | REQUIRES RESUBMIT | September 5, 2025 1st Review CMA, LLC. Attn: Chuck Meyer 1900 N. Fremont Avenue Tucson, Arizona 85719 Re: DOWNER OFFICE TENANT IMPROVEMENT City of Tucson Permit Number: TC-COM-1224-02280 Stantec Project Number: 185215066 Stantec File Number: TUC-25-088 Plan review for the above referenced project has been completed. This letter reflects comments to be addressed. PLEASE send all response to comments back to the City through the permit portal! Responses sent directly to Stantec will be ignored. Also, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed. Please cloud and delta all changes and provide a letter with a written response to each of the comments indicating the action taken. The scope of this review covers the architectural, structural, plumbing, mechanical, and electrical designs as they relate to the codes adopted by the jurisdiction. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions, and concerns before permit approval. Occupancy Group Construction Type Area (Square feet) Occupant Load Automatic Fire Sprinklers Fire Alarms B V-B 2,143 22 No No Separate Permits: None. Deferred Submittals: Type I hood. Special Inspections: Epoxy and expansion anchors. ARCHITECTURAL COMMENTS General 1. Please provide proof that this project has been submitted to the Pima County Health Department for permitting. Make sure to incorporate any of their comments into any future submittals. 2. Please provide City of Tucson special inspection certificate(s) with Parts A and B completed for epoxy and expansion anchors. Make sure that the owner or their legal representative signs the form. 3. Please remove the welding from the special inspections indicated on the cover. The structural design does not appear to require field welding. Sheet A1 1. The plans do not indicate a drinking fountain. Please provide and include in plumbing calculations on the cover sheet. [Ref. IPC 2018 Sec. 2902.1] 2. The plans do not indicate a service sink. Please provide and include in plumbing calculations on the cover sheet. [Ref. IPC 2018 Sec. 2902.1] 3. The proposed kitchen layout does not meet the minimum clearance requirements of 60” between cabinets, countertops, appliances, or walls within the kitchen work area for U-shaped kitchens. Please revise. [Ref. ICC A117.1-2009 Sec. 804.2.2] 4. The accessible bathroom at the hallway does not meet accessibility clearance requirements. The door swings within the clear floor space and fixture clearances, a 5’ turning radius does not appear to fit in the room, fixtures are not allowed within the water closet clearance. Please revise. [Ref. ICC A117.1-2009 Sec. 304 & 604] 5. Please provide the manufacturer’s specifications for the proposed kitchen equipment to help determine if kitchen hoods will be required for the proposed project. STRUCTURAL COMMENTS There are no comments. MECHANICAL COMMENTS There are no comments. PLUMBING COMMENTS There are no comments. ELECTRICAL COMMENTS There are no comments. Should you have any questions regarding the plan review comments, please contact the plan reviewer listed for the appropriate discipline. |
||
| 09/09/2025 | Fire New Construction Standard | REVIEW COMPLETED | |||
| 09/08/2025 | Historic | REVIEW COMPLETED | SD-0125-00003 BHHZAB conducted its review on 01/28/2025, and recommended approval with conditions. PRS conducted its review on 2/27/2025, and recommended approval with conditions. PDSD Director's Decision Notice was issued on 7/18/2025 [SD-0125-00003]. This completes the HPZ process. Historic full review fees are paid. The applicant may proceed to permitting with approved decision notice. No further HPZ review required. Please resubmit your HPZ approved Design Package and any construction drawing under the building permit [TC-COM-1224-02280] If you have any questions, contact Michael.Taku@tucsonaz.gov |
||
| 09/08/2025 | PDSD Application Completeness Express | REVIEW COMPLETED |