Permit Number: TC-COM-1223-02960
Parcel: 125091430

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.4

Permit Number - TC-COM-1223-02960
Review Name: COMMERCIAL REVIEW - FULL v.4
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
08/19/2025 Commercial Electrical APPROVED
08/28/2025 Commercial Mechanical APPROVED
08/28/2025 Bldg Permits - Post Review Express PENDING ASSIGNMENT
08/28/2025 Commercial Plumbing REQUIRES RESUBMIT ACTIVITY NO. TC-COM-1223-02960
ADDRESS/PARCEL: (2855 E BROADWAY BL TUCSON, AZ 85716)
Submit your revised drawings along with a detailed response letter, which states how all Building Review Section comments were addressed. The submitted documents were incomplete and a thorough plan review could not be performed. Please be aware, new comments may arise with the next review. Review will not proceed without the response letter.

COMMENTS:

1. Please clarify and accurately show on the plumbing drawing that you are providing a minimum of two drinking fountains that comply with section 410.3 IPC 2018. One accessible for standing persons and one accessible for persons confined to a wheelchair. Not able to find specs on Model #HS-STC5 1 2WH drinking fountain.
a. For the business occupancy, water coolers can be substituted for drinking fountains per IBC 2902.1 and IPC 410.1 Otherwise, drinking fountain shall be accessible per ICC A117.1 section 602 with required clear floor space and knee/toe clearance per section 306, 36 inches spout outlet height (30 inches for children), 38 inches minimum / 43 inches maximum for person standing (30 inches minimum / 43 inches maximum for children).
2. Provide tempered water for the lavatories and public hand-washing sinks in restrooms using approved devices conforming to ASSE 1070. Reference: Sections 419.5 and 607.1.2, IPC 2018
a. Mechanical mixing valve (Model # SLS-7000-DP4) does not appear to conform to ASSE 1070. Please clarify that the MAXLINE thermostatic mixing valve or equivalent will be used with the Symmons faucet.
08/28/2025 Water - PDSD REQUIRES RESUBMIT Please revise the site plan call-out from “backwater valve” to “backflow preventer.”
08/15/2025 PDSD Application Completeness Express REVIEW COMPLETED