Permit Number: TC-COM-1223-02947
Parcel: 125111560

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.2

Permit Number - TC-COM-1223-02947
Review Name: COMMERCIAL REVIEW - FULL v.2
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
04/12/2024 Bldg Permits - Post Review Express PENDING ASSIGNMENT MASTER SET OF CONSTRUCTION PLANS ARE LOCATED WITH PERMIT TC-COM-1223-02916/BLDG 9, AND COVER PERMITS TC-COM-1223-02945 (3701 E 3RD ST TUCSON, AZ 85716)/BLDG 2, TC-COM-1223-02946 (3701 E 3RD ST TUCSON, AZ 85716)/BLDG 3, TC-COM-1223-02947 (3701 E 3RD ST TUCSON, AZ 85716)/BLDG 4, TC-COM-1223-02948 (3701 E 3RD ST TUCSON, AZ 85716)/BLDG 5 & TC-COM-1223-02949 (3701 E 3RD ST TUCSON, AZ 85716)/BLDG 6
04/11/2024 Site Engineering REQUIRES RESUBMIT The building permit cannot be approved until the associated development package, TD-DEV-1023-00438, has been approved.

Lianne Evans
lianne.evans@tucsonaz.gov
04/12/2024 Site Zoning REQUIRES RESUBMIT MASTER SET OF CONSTRUCTION PLANS ARE LOCATED WITH PERMIT TC-COM-1223-02916/BLDG 9, AND COVER PERMITS TC-COM-1223-02945 (3701 E 3RD ST TUCSON, AZ 85716)/BLDG 2, TC-COM-1223-02946 (3701 E 3RD ST TUCSON, AZ 85716)/BLDG 3, TC-COM-1223-02947 (3701 E 3RD ST TUCSON, AZ 85716)/BLDG 4, TC-COM-1223-02948 (3701 E 3RD ST TUCSON, AZ 85716)/BLDG 5 & TC-COM-1223-02949 (3701 E 3RD ST TUCSON, AZ 85716)/BLDG 6

FROM: PDSD Zoning Review Section

PROJECT: TC-COM-1223-02916, TC-COM-1223-02945, TC-COM-1223-02946, TC-COM-1223-02947, TC-COM-1223-02948 & TC-COM-1223-02949 - TD-DEV-1023-00438
3701 E 3RD ST. (R-3)
MULTI-FAMILY AND RESIDENTIAL CARE SERVICES (1st Review)

TRANSMITTAL DATE:‎ April 12, 2024

COMMENTS: Please resubmit revised drawings along with a detailed response letter, which states how all Zoning Review Section comments were addressed.

This site is located in the R-3 zone (UDC 4.7.12). MULTI-FAMILY AND RESIDENTIAL CARE SERVICES AND ARE SUBJECT TO USE SPECIFIC STANDARDS 4.9.7.B.6. RESIDENTIAL CARE SERVICES ARE SUBJECT TO SPECIFIC STANDARDS 4.9.7.J.2.b, 3.d, 4, .8.

1. Zoning has reviewed the building plans for compliance with Development Package (DP) TD-DEV-1023-00438 and although it appears that the plans match, until the DP is approved by all review agencies Zoning cannot approve the building plans.

If you have any questions about this transmittal, please contact If you have any questions about this transmittal, please contact Zone1.desk@tucsonaz.gov.
03/20/2024 External Reviewers - SAFEBuilt REVIEW COMPLETED Structural(S) Reviewer
Madeline Nelson
mnelson@safebuilt.com
Approved with Comments
Reason:
Date Completed : 3/16/2024 5:46:18 PM
GENERAL - DEFERRED SUBMITTAL REQUIREMENTS: The engineer of record has stated that design of the prefabricated wood trusses shall be accomplished by Deferred Submittal. Please note that IBC Section 107.3.4.1 requires deferred
submittals to be approved by the building official. The IBC further requires the following procedure be followed when permitting deferred submittals:

1. All submittals shall first be reviewed by design professional in responsible charge.

2. Design professional shall affix a notation that the deferred items are in general conformance with their design of the building.

3. They shall then be submitted for review by the building official.

4. No structural elements shall be installed until approved by building official.


Building(B) Reviewer
Andrew Bevis
abevis@safebuilt.com
Approved
Reason:
Date Completed : 3/15/2024 3:28:12 PM



Mechanical(M) Reviewer
Jorge Valido
jvalido@safebuilt.com
Approved
Reason:
Date Completed : 3/18/2024 11:40:30 AM
1. Plan sheet M201 - Range hood Exhaust duct shall be independent of all other exhaust systems - 2018 International Mechanical Code Section M1503.3 Exhaust Discharge (RESOLVED)

2. General - Provide a diagram/Drawing of condensate disposal. Show condensate line and termination point/discharge of condensate. For the PTAC units (RESOLVED)




Electrical(E) Reviewer
Ron Ross
rross@safebuilt.com
Approved
Reason:
Date Completed : 3/15/2024 11:04:12 AM



Plumbing(P) Reviewer
Perry Hendershott
phendershott@safebuilt.com
Approved
Reason:
Date Completed : 3/18/2024 9:46:22 PM
Second Plumbing Review:
Resolved-1). Plan page A102 and or plumbing plans need to include the roof drainage method & calculations. -IPC 1101.7

Resolved-2).The communal Kitchen sinks throughout the plumbing pages need to discharge thru a grease interceptor. -IPC 1003.1 & Tucson Amendments- **NOT Required Per Utility Authority**
03/14/2024 PDSD Application Completeness Express REVIEW COMPLETED