| 04/12/2024 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | MASTER SET OF CONSTRUCTION PLANS ARE LOCATED WITH PERMIT TC-COM-1223-02916/BLDG 9, AND COVER PERMITS TC-COM-1223-02945 (3701 E 3RD ST TUCSON, AZ 85716)/BLDG 2, TC-COM-1223-02946 (3701 E 3RD ST TUCSON, AZ 85716)/BLDG 3, TC-COM-1223-02947 (3701 E 3RD ST TUCSON, AZ 85716)/BLDG 4, TC-COM-1223-02948 (3701 E 3RD ST TUCSON, AZ 85716)/BLDG 5 & TC-COM-1223-02949 (3701 E 3RD ST TUCSON, AZ 85716)/BLDG 6 | ||
| 04/11/2024 | Site Engineering | REQUIRES RESUBMIT | The building permit cannot be approved until the associated development package, TD-DEV-1023-00438, has been approved. Lianne Evans lianne.evans@tucsonaz.gov |
||
| 04/12/2024 | Site Zoning | REQUIRES RESUBMIT | MASTER SET OF CONSTRUCTION PLANS ARE LOCATED WITH PERMIT TC-COM-1223-02916/BLDG 9, AND COVER PERMITS TC-COM-1223-02945 (3701 E 3RD ST TUCSON, AZ 85716)/BLDG 2, TC-COM-1223-02946 (3701 E 3RD ST TUCSON, AZ 85716)/BLDG 3, TC-COM-1223-02947 (3701 E 3RD ST TUCSON, AZ 85716)/BLDG 4, TC-COM-1223-02948 (3701 E 3RD ST TUCSON, AZ 85716)/BLDG 5 & TC-COM-1223-02949 (3701 E 3RD ST TUCSON, AZ 85716)/BLDG 6 FROM: PDSD Zoning Review Section PROJECT: TC-COM-1223-02916, TC-COM-1223-02945, TC-COM-1223-02946, TC-COM-1223-02947, TC-COM-1223-02948 & TC-COM-1223-02949 - TD-DEV-1023-00438 3701 E 3RD ST. (R-3) MULTI-FAMILY AND RESIDENTIAL CARE SERVICES (1st Review) TRANSMITTAL DATE: April 12, 2024 COMMENTS: Please resubmit revised drawings along with a detailed response letter, which states how all Zoning Review Section comments were addressed. This site is located in the R-3 zone (UDC 4.7.12). MULTI-FAMILY AND RESIDENTIAL CARE SERVICES AND ARE SUBJECT TO USE SPECIFIC STANDARDS 4.9.7.B.6. RESIDENTIAL CARE SERVICES ARE SUBJECT TO SPECIFIC STANDARDS 4.9.7.J.2.b, 3.d, 4, .8. 1. Zoning has reviewed the building plans for compliance with Development Package (DP) TD-DEV-1023-00438 and although it appears that the plans match, until the DP is approved by all review agencies Zoning cannot approve the building plans. If you have any questions about this transmittal, please contact If you have any questions about this transmittal, please contact Zone1.desk@tucsonaz.gov. |
||
| 03/20/2024 | External Reviewers - SAFEBuilt | REVIEW COMPLETED | Structural(S) Reviewer Madeline Nelson mnelson@safebuilt.com Approved with Comments Reason: Date Completed : 3/16/2024 5:46:18 PM GENERAL - DEFERRED SUBMITTAL REQUIREMENTS: The engineer of record has stated that design of the prefabricated wood trusses shall be accomplished by Deferred Submittal. Please note that IBC Section 107.3.4.1 requires deferred submittals to be approved by the building official. The IBC further requires the following procedure be followed when permitting deferred submittals: 1. All submittals shall first be reviewed by design professional in responsible charge. 2. Design professional shall affix a notation that the deferred items are in general conformance with their design of the building. 3. They shall then be submitted for review by the building official. 4. No structural elements shall be installed until approved by building official. Building(B) Reviewer Andrew Bevis abevis@safebuilt.com Approved Reason: Date Completed : 3/15/2024 3:28:12 PM Mechanical(M) Reviewer Jorge Valido jvalido@safebuilt.com Approved Reason: Date Completed : 3/18/2024 11:40:30 AM 1. Plan sheet M201 - Range hood Exhaust duct shall be independent of all other exhaust systems - 2018 International Mechanical Code Section M1503.3 Exhaust Discharge (RESOLVED) 2. General - Provide a diagram/Drawing of condensate disposal. Show condensate line and termination point/discharge of condensate. For the PTAC units (RESOLVED) Electrical(E) Reviewer Ron Ross rross@safebuilt.com Approved Reason: Date Completed : 3/15/2024 11:04:12 AM Plumbing(P) Reviewer Perry Hendershott phendershott@safebuilt.com Approved Reason: Date Completed : 3/18/2024 9:46:22 PM Second Plumbing Review: Resolved-1). Plan page A102 and or plumbing plans need to include the roof drainage method & calculations. -IPC 1101.7 Resolved-2).The communal Kitchen sinks throughout the plumbing pages need to discharge thru a grease interceptor. -IPC 1003.1 & Tucson Amendments- **NOT Required Per Utility Authority** |
||