Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL PDSD SIMPLE REVIEW v.2
Permit Number - TC-COM-1223-02940
Review Name: COMMERCIAL PDSD SIMPLE REVIEW v.2
Review Status: Requires Resubmit
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
02/15/2024 | Bldg Permits - Post Review | PENDING ASSIGNMENT | |||
02/15/2024 | Commercial Electrical | REQUIRES RESUBMIT | Please address the electrical plan review comments and provide a written response. Describe in detail the scope of electrical work to be performed. Provide complete electrical plans including a site plan that shows the exact location for the proposed new service and locations of any existing electrical services on the parcel. Provide compliance with NEC 230.2 if applicable. Provide a complete electrical line diagram. Correlate plans with the scope of work description. Electrical design, calculations, are to be performed by a registrant registered in the state of Arizona, including sealed electrical plans. Ref; 2018 IBC section 107.2.1, 2017 NEC, 2012 City of Tucson Commercial Plan Submittal Requirements. | ||
02/14/2024 | PDSD Application Completeness | REVIEW COMPLETED |