Permit Number: TC-COM-1223-02911
Parcel: 11504310A

Review Status: Requires Resubmit

Review Details: BUILDING DEFERRED SUBMITTAL REVIEW v.2

Permit Number - TC-COM-1223-02911
Review Name: BUILDING DEFERRED SUBMITTAL REVIEW v.2
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
09/05/2025 Bldg Permits - Post Review Express PENDING ASSIGNMENT
09/05/2025 External Reviewers - SAFEBuilt Express REQUIRES RESUBMIT Building(B) Reviewer
Kimiyoshi Shimabukuro
kshimabukuro@safebuilt.com
Denied
Reason:
Date Completed : 9/5/2025 5:38:36 AM
1. Page 21 of 47 / Isolate Footing / Reinforcing steel observation report of isolated footing status shows that “DOES NOT
Comply.”: Further compliance statements did not appear to be complete in accordance with project plans and
specifications. Please provide referred deviated or revised detail and specification from the registered design
professional. Page 26 of 47 shows detail 3 from sheet SU1.1 with 6’-0” depth.
09/02/2025 PDSD Application Completeness Express REVIEW COMPLETED