Permit Number: TC-COM-1223-02903
Parcel: 13502134K

Address:
7050 E 22ND ST

Review Status: Approved

Review Details: COMMERCIAL REVIEW - FULL v.3

Permit Number - TC-COM-1223-02903
Review Name: COMMERCIAL REVIEW - FULL v.3
Review Status: Approved
Review Date Reviewer's Name Type of Review Description Status Comments
04/15/2024 Bldg Permits - Post Review REVIEW COMPLETED
04/15/2024 External Reviewers - SAFEBuilt REVIEW COMPLETED Structural(S) Reviewer
Madeline Nelson
mnelson@safebuilt.com
Approved
Reason:
Date Completed : 1/4/2024 2:02:25 PM



Building(B) Reviewer
Andrew Bevis
abevis@safebuilt.com
Approved
Reason:
Date Completed : 2/20/2024 10:02:55 AM



Mechanical(M) Reviewer
Jorge Valido
jvalido@safebuilt.com
Approved
Reason:
Date Completed : 1/3/2024 1:27:17 PM




Electrical(E) Reviewer
Ron Ross
rross@safebuilt.com
Approved with Comments
Reason:
Date Completed : 1/4/2024 9:05:22 AM
ELECTRICAL REVIEW OF KROGER
BY: RON ROSS PE
Approved with comments for electrical
ED1.2 POWER DEMOLITION PLAN: Could not locate Keynote 4
E1.3 ELECTRICAL POWER PLAN: Missing numerous Keynotes.



Plumbing(P) Reviewer
Perry Hendershott
phendershott@safebuilt.com
Approved with Comments
Reason:
Date Completed : 4/11/2024 4:40:14 PM
Third Plumbing Review: OK Subject to Field Inspections
Resolved-1)., Need to address Building plan review comment 1 -IPC 403.1

Resolved2). Lavatories on P6.1 Fixture schedule needs ASSE 1070 mixing valves- IPC 419.5

Resolved-3). DW-1 in bakery on plan page P1.1 needs to discharge to the grease system. -Tucson Plumbing code amendments ** added Hydromechanical grease interreceptor can't receive waste from a dishwasher Per Tucson Plumbing code amendments for 2018 IPC Chapter 10** Would need to connect to a gravity grease interceptor
04/08/2024 PDSD Application Completeness REVIEW COMPLETED