Permit Number: TC-COM-1223-02903
Parcel: 13502134K

Address:
7050 E 22ND ST

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-1223-02903
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
12/27/2023 Site Zoning APPROVED
01/23/2024 Site Engineering NOT REQUIRED
01/23/2024 Bldg Permits - Post Review PENDING ASSIGNMENT
01/09/2024 External Reviewers - SAFEBuilt REQUIRES RESUBMIT Structural(S) Reviewer
Madeline Nelson
mnelson@safebuilt.com
Approved
Reason:
Date Completed : 1/4/2024 2:02:25 PM




Building(B) Reviewer
Andrew Bevis
abevis@safebuilt.com
Denied
Reason:
Date Completed : 12/29/2023 10:12:33 PM
1. General: No occupant load calculations provided. Provide a detailed existing and new occupant load calculation in accordance with 2018 IBC Section 1004.



Mechanical(M) Reviewer
Jorge Valido
jvalido@safebuilt.com
Approved
Reason:
Date Completed : 1/3/2024 1:27:17 PM



Electrical(E) Reviewer
Ron Ross
rross@safebuilt.com
Approved with Comments
Reason:
Date Completed : 1/4/2024 9:05:22 AM
ELECTRICAL REVIEW OF KROGER
BY: RON ROSS PE
Approved with comments for electrical
ED1.2 POWER DEMOLITION PLAN: Could not locate Keynote 4

E1.3 ELECTRICAL POWER PLAN: Missing numerous Keynotes.



Plumbing(P) Reviewer
Perry Hendershott
phendershott@safebuilt.com
Denied
Reason:
Date Completed : 1/7/2024 11:30:23 PM
First Plumbing Review:
1)., Need to address Building plan review comment 1 -IPC 403.1

2). Lavatories on P6.1 Fixture schedule needs ASSE 1070 mixing valves- IPC 419.5

3). DW-1 in bakery on plan page P1.1 needs to discharge to the grease system. -Tucson Plumbing code amendments
12/27/2023 Fire New Construction REVIEW COMPLETED
12/22/2023 PDSD Application Completeness REVIEW COMPLETED
01/22/2024 Water - PDSD REVIEW COMPLETED