Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: TC-COM-1223-02903
Parcel: 13502134K

Address:
7050 E 22ND ST

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.2

Permit Number - TC-COM-1223-02903
Review Name: COMMERCIAL REVIEW - FULL v.2
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
02/28/2024 Bldg Permits - Post Review Express PENDING ASSIGNMENT
02/28/2024 External Reviewers - SAFEBuilt REQUIRES RESUBMIT Structural(S) Reviewer
Madeline Nelson
mnelson@safebuilt.com
Approved
Reason:
Date Completed : 1/4/2024 2:02:25 PM



Building(B) Reviewer
Andrew Bevis
abevis@safebuilt.com
Approved
Reason:
Date Completed : 2/20/2024 10:02:55 AM



Mechanical(M) Reviewer
Jorge Valido
jvalido@safebuilt.com
Approved
Reason:
Date Completed : 1/3/2024 1:27:17 PM



Electrical(E) Reviewer
Ron Ross
rross@safebuilt.com
Approved with Comments
Reason:
Date Completed : 1/4/2024 9:05:22 AM
ELECTRICAL REVIEW OF KROGER
BY: RON ROSS PE
Approved with comments for electrical
ED1.2 POWER DEMOLITION PLAN: Could not locate Keynote 4
E1.3 ELECTRICAL POWER PLAN: Missing numerous Keynotes.



Plumbing(P) Reviewer
Perry Hendershott
phendershott@safebuilt.com
Denied
Reason:
Date Completed : 2/21/2024 10:23:19 PM
Second Plumbing Review:
Resolved-1)., Need to address Building plan review comment 1 -IPC 403.1

Resolved2). Lavatories on P6.1 Fixture schedule needs ASSE 1070 mixing valves- IPC 419.5

Unresolved-3). DW-1 in bakery on plan page P1.1 needs to discharge to the grease system. -Tucson Plumbing code amendments ** added Hydromechanical grease interreceptor can't receive waste from a dishwasher Per Tucson Plumbing code amendments for 2018 IPC Chapter 10** Would need to connect to a gravity grease interceptor
02/16/2024 PDSD Application Completeness Express REVIEW COMPLETED