Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
03/11/2024 | Bldg Permits - Post Review | PENDING ASSIGNMENT | |||
03/11/2024 | Commercial Electrical | REQUIRES RESUBMIT | Please address the electrical plan review comments and provide a written response. 1 Indicate all branch circuit and panel designations on the electrical floor plan, NEC art 408.4 2 Show any proposed lighting changes if applicable. 3 Provide a complete panel schedule including loads calculations for the panel, NEC art 408. Ref; 2018 IBC section 107.2.1, 2017 NEC, City of Tucson Commercial Plan Submittal Requirements. |
||
02/23/2024 | PDSD Application Completeness | REVIEW COMPLETED |