Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-1223-02845
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
12/15/2023 Commercial Structural APPROVED
12/15/2023 Bldg Permits - Post Review PENDING ASSIGNMENT
12/15/2023 Commercial Electrical REQUIRES RESUBMIT Please address the electrical plan review comments and provide a written response.

1. Ref; Plan Sheet ‘a1.10’, ‘a1.11’, ‘a1.12’, a1.20, a1.21, a1., and response to electrical comments.

(a) Per electrical plan review response letter note #5,” No electrical plans are required as no changes are provided, all existing to remain. Notes on plans have been corrected.”. There is a discrepancy Plan Sheet ‘a1.10, ‘a1.11’, ‘a1.12’, ‘a1.20’, ‘a1.21’. Per the ‘Typ. Lighting Note states, All existing Lighting locations to be replaced with New Lighting’, and the ‘Electrical note’ “All Existing Power and Lights to Remain”. Please clarify on the plans.

Ref; 2018 IBC section 107.2.1, 2017 NEC, 2018 IECC.
12/15/2023 Commercial Mechanical REQUIRES RESUBMIT The exhaust airflow requirement for kitchen hoods in R-2, R-3, and R-4 occupancies is 100 CFM for intermittent operation or 25 CFM for continuous operation. Reference: footnote f, Table 403.3.1.1IMC 2018 and Section 403.3.2.3, IMC 2018. [Initial comment: As new work, the hoods for the ranges must either provide the minimum kitchen ventilation called for in Table 403.3.1.1, IMC 2018, or if the hoods are ductless, local exhaust shall be provided for the kitchen per Section 403.3.2.3, IMC 2018. Reference: Section 505.3, exception 1, IMC 2018.]
12/15/2023 PDSD Application Completeness REVIEW COMPLETED Copied from Master permit - TC-COM-0723-01695