Permit Number: TC-COM-1223-02830
Parcel: 128010190

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-1223-02830
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
01/09/2024 Commercial Structural APPROVED
01/16/2024 Bldg Permits - Post Review PENDING ASSIGNMENT
01/16/2024 Commercial Electrical REQUIRES RESUBMIT Please address the electrical plan review comments and provide a written response.

1. Provide complete compliance with the 2012 City of Tucson Outdoor Lighting Code for the exterior lighting. See section 104 for plan submittal requirements.

2. Provide complete compliance with the 2018 IECC for exterior lighting.

3. Ref; ‘Line diagram’, ‘Supercharger AC Circuit Schedule 'and ‘Load Schedule’ for ‘SB-1’. The line diagram shows a 175 Amp OCPD feeding ‘SD-XR' and the Load Schedule shows a 225 Amp OCPD feeding ‘SDXR’. Also, there is no feeder identification for the primary and secondary conductors for the Transformer ‘SDXR’. Please clarify.

4. Ref; ‘Electrical Site Plan E-101', and ‘Line Diagram’ E-201. Please show the location of Distribution Board ‘DB-1’ on the ‘Electrical Site Plan’.

Ref; 2018 IBC section 107.2.1, 2017 NEC, 2018 IECC, 2012 City of Tucson Outdoor Lighting Code.
01/11/2024 Site Engineering REQUIRES RESUBMIT This project is within a regulated floodplain and requires a Floodplain Use Permit (FUP.)
Please start a new FUP at our permit application web page:
https://tdc-online.tucsonaz.gov/#/home
NOTE: Documentation of a cost estimate from your contractor will be required if this project involves any reconstruction, repair, rehabilitation, structurally connected addition, or other improvement of an existing structure (including TIs and solar). Construction of separate builds/new structures does not require a cost estimate to be provided. Construction of new buildings require elevation one foot above the base flood elevation, which may require that the foundation of the building be raised as much as two feet above the existing elevation onsite. Storage buildings with no utilities may be wet floodproofed using flood vents. For all new construction buildings, two elevation certificates must be filled out by a registered land surveyor and submitted to the City, one before the foundation is poured and one after construction is completed.
Instructions:
1. Navigate into the current project in the “My Work” tab. Within the permit, navigate to the “Sub-Records” tab and click “Apply” on the Floodplain Use Permit Sub-Record
2. Locations -> Confirm the location is accurate to the project. Click “Next”
3. Type -> Fill in the “Square Feet” and “Valuation” boxes with the project area and a contractor-provided cost estimate (See note above: for new structures, input 0). Click “Next”
4. Contacts -> Confirm contacts and add any additional contacts if applicable. Click “Next”
5. More Info -> This will be filled in by the engineer assigned to your case, Click “Next”
6. Attachments -> Please attach the project plan, supporting documentation for the cost estimate (if applicable), and a drainage/hydrology report (if applicable). Click “Next”
7. Signature -> Read the statement and type your name. Sign your name below (You may Enable Type Signature to have the software sign for you.) Click “Next”
8. Review and Submit -> Review all information to ensure accuracy. Click “Submit”
Contact Lianne Evans at lianne.evans@tucsonaz.gov or Stephen Blood at Stephen.Blood@tucsonaz.gov if you have any questions about the FUP.
12/26/2023 Site Zoning REQUIRES RESUBMIT ZONING REVIEW TRANSMITTAL

FROM: PDSD Zoning Review

PROJECT:
TC-COM-1223-02830
6228 E BROADWAY BL. – C-1
Install 28 Telsa EV Charging stations (1st Review)

TRANSMITTAL: December 26, 2023

Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed.

This site is located in the C-1 zone (UDC 4.7.20).

1. Per UDC Figure 7.4.6-A and Table 7.4.6-1 the minimum parking space depth for 90 degree parking spaces is 18’-0”. The plans call out 17’ parking space depths. Clearly demonstrate that the proposed EV equipment does not encroach into the required 1’ vehicle overhang at the 17’-0” deep parking spaces.

2. Clearly demonstrate that the required 4’-0” sidewalk width, TSM Section 7-01.4.3.A, is maintained along the west side of the building and between the handrail and the south most EV equipment.

3. Provide a width dimension for the proposed accessible ramps shown on the plan .

If you have any questions about this transmittal, please contact Zone1.desk@tucsonaz.gov.
12/18/2023 PDSD Application Completeness REVIEW COMPLETED