Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL PDSD SIMPLE REVIEW v.1
Permit Number - TC-COM-1223-02813
Review Name: COMMERCIAL PDSD SIMPLE REVIEW v.1
Review Status: Requires Resubmit
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
12/11/2023 | Bldg Permits - Post Review | PENDING ASSIGNMENT | |||
12/11/2023 | Commercial Mechanical | REQUIRES RESUBMIT | Provide the manufacturer’s equipment data and installation instructions for the new space heaters. Reference: Sections 301 and 304.1, IMC 2018. | ||
12/11/2023 | Commercial Plumbing | REQUIRES RESUBMIT | 1. Gas piping sketches by licensed plumbers are intended for replacement of existing fuel gas piping in commercial installations. It is not for revisions or additions to existing commercial fuel gas piping systems; the revisions and additions require plans produced by an Arizona Registrant. Reference: Section 107.1, IBC 2018). 2. Show the complete natural gas distribution system served by the gas meter. Provide all the connected loads and the developed pipe lengths to each load served by the gas meter. Reference: Section 402.2, IFGC 2018. |
||
12/11/2023 | PDSD Application Completeness | REVIEW COMPLETED |