Review Status: Requires Resubmit

Review Details: COMMERCIAL PDSD SIMPLE REVIEW v.1

Permit Number - TC-COM-1223-02813
Review Name: COMMERCIAL PDSD SIMPLE REVIEW v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
12/11/2023 Bldg Permits - Post Review PENDING ASSIGNMENT
12/11/2023 Commercial Mechanical REQUIRES RESUBMIT Provide the manufacturer’s equipment data and installation instructions for the new space heaters. Reference: Sections 301 and 304.1, IMC 2018.
12/11/2023 Commercial Plumbing REQUIRES RESUBMIT 1. Gas piping sketches by licensed plumbers are intended for replacement of existing fuel gas piping in commercial installations. It is not for revisions or additions to existing commercial fuel gas piping systems; the revisions and additions require plans produced by an Arizona Registrant. Reference: Section 107.1, IBC 2018).
2. Show the complete natural gas distribution system served by the gas meter. Provide all the connected loads and the developed pipe lengths to each load served by the gas meter. Reference: Section 402.2, IFGC 2018.
12/11/2023 PDSD Application Completeness REVIEW COMPLETED