Permit Number: TC-COM-1223-02796
Parcel: 12509012A

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.2

Permit Number - TC-COM-1223-02796
Review Name: COMMERCIAL REVIEW - FULL v.2
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
03/18/2024 External Reviewers - Stantec APPROVED
04/22/2024 Bldg Permits - Post Review PENDING ASSIGNMENT
04/14/2024 Fire New Construction REQUIRES RESUBMIT -Provide updated door schedule showing required hardware (panic hardware) for required doors per IFC 1010.1.10
-Provide an approved petition of appeal, from the BO, for your OL appeal.
john.vincent@tucsonaz.gov
5203495581
04/22/2024 Site Zoning REQUIRES RESUBMIT Provide the site plan as part of the full plan set. The site plan should be added as a sheet, as opposed to a separate reference sheet.

Please ensure the height and square footage of the building are provided. Please also ensure the building in question is highlighted on the site plan.

Zoning will be comparing the site plan to the DP to ensure they match.

Nicholas.Martell@tucsonaz.gov
03/16/2024 PDSD Application Completeness REVIEW COMPLETED