Permit Number: TC-COM-1223-02792
Parcel: 13312004H

Review Status: Requires Resubmit

Review Details: COMMERCIAL PDSD SIMPLE REVIEW v.1

Permit Number - TC-COM-1223-02792
Review Name: COMMERCIAL PDSD SIMPLE REVIEW v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
12/18/2023 Bldg Permits - Post Review Express PENDING ASSIGNMENT
12/18/2023 Commercial Electrical REQUIRES RESUBMIT Please address the electrical plan review comments and provide a written response
1. This is a commercial project, requiring all documents to be prepared, sealed, signed, and dated by a registered design professional. Provide complete electrical plans, design, and calculations, sealed by an Arizona Registrant. Reference: Arizona Revised Statutes 32-125, Board of Technical Registration Rules R4-30-304, 2018 IBC section 107.1, 2017 NEC, City of Tucson Commercial Plan Submittal Requirements
12/12/2023 Commercial Mechanical REQUIRES RESUBMIT 1. Provide plans sealed by an Arizona Registrant. Reference: Arizona Revised Statutes 32-125, Board of Technical Registration Rules R4-30-304.
2. Show that the proposed rooftop units meet the requirements of Sections C403.3, C403.4, and C403.5 (e.g. provide the mechanical compliance certification from COMcheck). Reference: Section C501.4, International Energy Conservation Code 2018.
3. The sketch appears to show six packaged AC units with a total cooling capacity of 409 MBH and 250 MBH sensible capacity being installed. The cooling load calculation do not, however, include any information regarding the cooling load caused by the people in this assembly occupancy.
4. Provide the manufacturer’s equipment data for the new rooftop units. Reference: Sections 301 and 304.1, IMC 2018.
5. Show the size, routing, and termination of the condensate drains. Reference: Section 307.2.1, IMC 2018 as amended by the City of Tucson.
6. Provide calculations to verify that adequate ventilation will be provided for the occupied spaces. Reference: Section 403.3.1.1, IMC 2018.
12/12/2023 Commercial Plumbing REQUIRES RESUBMIT Provide a natural gas piping design for the building, including the piping layout on a roof plan and a natural gas schematic showing the sizes, loads and developed lengths of the piping for the new AC units and any existing appliances that will continue to operate. Reference: Section 107.2.1, IBC 2018.
12/06/2023 PDSD Application Completeness Express REVIEW COMPLETED