Permit Number: TC-COM-1223-02789
Parcel: 116182220

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.2

Permit Number - TC-COM-1223-02789
Review Name: COMMERCIAL REVIEW - FULL v.2
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
03/01/2024 Bldg Permits - Post Review Express PENDING ASSIGNMENT
02/08/2024 External Reviewers - SAFEBuilt REQUIRES RESUBMIT Structural(S) Reviewer
Madeline Nelson
mnelson@safebuilt.com
Approved
Reason:
Date Completed : 12/20/2023 10:40:13 AM



Building(B) Reviewer
Andrew Bevis
abevis@safebuilt.com
Approved
Reason:
Date Completed : 12/18/2023 5:20:32 PM



Mechanical(M) Reviewer
Jorge Valido
jvalido@safebuilt.com
Denied
Reason:
Date Completed : 2/5/2024 10:49:11 AM

1. General - Provide Manufacturer Hood Plans - 2018 International Mechanical Code section 507.1 - 2018 International Energy Conservation Code Section C103.2Information on construction documents (4) (UNRESOLVED)

i. Provide Manufacturer Hood LISTED plans.- 2018 International Mechanical Code section 507.1 - 2018 International Energy Conservation Code Section C103.2 Information on construction documents (4)

2. General - Provide Manufacturer Fire Suppression Plans - 2018 International Mechanical Code Section 509.1 - 2018 International Energy Conservation Code Section C103.2Information on construction documents (4) (UNRESOLVED)

i. Provide Manufacturer Fire Suppression LISTED plans.- 2018 International Mechanical Code section 507.1 - 2018 International Energy Conservation Code Section C103.2Information on construction documents (4)

3. General - Provide Roof Plan. Show on roof plan all distances from edge of building to HVAC equipment and Hood supply and exhaust equipment. If applicable provide Guards for all equipment - 2018 International Mechanical Code Section [BE] 304.11. (RESOLVED)



Electrical(E) Reviewer
Ron Ross
rross@safebuilt.com
Approved with Comments
Reason:
Date Completed : 12/14/2023 12:57:29 PM
Electrical Review of Meteor Café
By: Ron Ross PE
E2.0 POWER PLAN:
Some numbers do not correlate to the panel schedule descriptions.

Would suggest to relocate electrical panels from utility room between Janitor’s sink and Water Heater. Suggestion only, as design is code compliant, but may receive
negative feedback from a local field inspector.



Plumbing(P) Reviewer
Perry Hendershott
phendershott@safebuilt.com
Denied
Reason:
Date Completed : 2/7/2024 11:04:00 PM
Second Plumbing Review:
Unresolved-1). Hydro mechanical grease interceptor on plan page G250 on plan page P1 can only receive discharge from 4 fixtures & Zero dishwashers per Tucson Plumbing Code Amendments. ** Per the Schier Website The GB-250 is not a gravity
grease interceptor see models at https://schierproducts.com/shop **

Resolved-2). Water connection to Number 53 beer dispenser on plan page P5 needs backflow protection, -IPC 608.17

Resolved-3). Add Gas sizing table used & system legnth to plan page P3 -IFGC 402.3

Resolved-4). Grease interceptor on plan page P1 needs to be vented. -IPC 1003.9
02/29/2024 Site Engineering REQUIRES RESUBMIT 1. Site Engineering cannot approve TC-COM-1223-02789 until the associated development package, TD-DEV-1022-00004, is approved.

Lianne Evans
lianne.evans@tucsonaz.gov
03/01/2024 Site Zoning REQUIRES RESUBMIT ZONING REVIEW TRANSMITTAL

FROM: Wyatt Berger
Lead Planner

PROJECT: TC-COM-1223-02789
901 West Congress Street – C-1
The Meteor Cafe (2nd Review)

TRANSMITTAL DATE: March 1, 2024

Please resubmit revised drawings with a detailed response letter stating how all Zoning Review Section comments were addressed.

1. Zoning has reviewed the building plans for compliance with the associated development package TD-DEV-1022-00004. Although it appears the building plan footprint, building height, and square footage are consistent with the submitted development package, Zoning cannot approve TC-COM-1223-02789 until the associated development package is approved.

If you have any questions about this transmittal, contact me at Wyatt.Berger@tucsonaz.gov or at 520-837-4951.
02/29/2024 Fire New Construction REVIEW COMPLETED
02/02/2024 PDSD Application Completeness Express REVIEW COMPLETED