Permit Number: TC-COM-1223-02789
Parcel: 116182220

Review Status: Approved

Review Details: COMMERCIAL REVIEW - FULL v.3

Permit Number - TC-COM-1223-02789
Review Name: COMMERCIAL REVIEW - FULL v.3
Review Status: Approved
Review Date Reviewer's Name Type of Review Description Status Comments
04/16/2024 Site Engineering APPROVED
04/15/2024 Site Zoning APPROVED
04/16/2024 Bldg Permits - Post Review Express REVIEW COMPLETED
03/22/2024 External Reviewers - SAFEBuilt REVIEW COMPLETED Structural(S) Reviewer
Madeline Nelson
mnelson@safebuilt.com
Approved
Reason:
Date Completed : 12/20/2023 10:40:13 AM



Building(B) Reviewer)
Andrew Bevis
abevis@safebuilt.com
Approved
Reason:
Date Completed : 12/18/2023 5:20:32 PM



Mechanical(M) Reviewer
Jorge Valido
jvalido@safebuilt.com
Approved
Reason:
Date Completed : 3/20/2024 11:50:38 AM
1. General - Provide Manufacturer Hood Plans - 2018 International Mechanical Code section 507.1 - 2018 International Energy Conservation Code Section C103.2 Information on construction documents (4)

i. Provide Manufacturer Hood LISTED plans.- 2018 International Mechanical Code section 507.1 - 2018 International Energy Conservation Code Section C103.2Information on construction documents (4) (RESOLVED)

2. General - Provide Manufacturer Fire Suppression Plans - 2018 International Mechanical Code Section 509.1 - 2018 International Energy Conservation Code Section C103.2Information on construction documents (4) Provide Manufacturer Fire Suppression LISTED plans.- 2018

i. International Mechanical Code section 507.1 - 2018 International Energy Conservation Code Section C103.2Information on construction documents (4) (RESOLVED)



Electrical(E) Reviewer
Ron Ross
rross@safebuilt.com
Approved with Comments
Reason:
Date Completed : 12/14/2023 12:57:29 PM
Electrical Review of Meteor Café
By: Ron Ross PE
E2.0 POWER PLAN:
Some numbers do not correlate to the panel schedule descriptions.

Would suggest to relocate electrical panels from utility room between Janitor’s sink and Water Heater. Suggestion only, as design is code compliant, but may receive negative feedback from a local field inspector.



Plumbing(P) Reviewer
Perry Hendershott
phendershott@safebuilt.com
Approved with Comments
Reason:
Date Completed : 3/20/2024 9:19:31 PM
Third Plumbing Review: OK Subject to Field inspections
Resolved-1). Hydro mechanical grease interceptor on plan page G250 on plan page P1 can only receive discharge from 4 fixtures & Zero dishwashers per Tucson Plumbing Code Amendments. ** Per the Schier Website The GB-250 is not a gravity
grease interceptor see models at https://schierproducts.com/shop ****See Attached Email From Utility Authority allowing this Grease Interceptor**

Resolved-2). Water connection to Number 53 beer dispenser on plan page P5 needs backflow protection, -IPC 608.17

Resolved-3). Add Gas sizing table used & system legnth to plan page P3 -IFGC 402.3

Resolved-4). Grease interceptor on plan page P1 needs to be vented. -IPC 1003.9
03/16/2024 PDSD Application Completeness Express REVIEW COMPLETED