Permit Number: TC-COM-1223-02776
Parcel: 134270080

Review Status: Requires Resubmit

Review Details: COMMERCIAL PDSD SIMPLE REVIEW v.1

Permit Number - TC-COM-1223-02776
Review Name: COMMERCIAL PDSD SIMPLE REVIEW v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
12/19/2023 Commercial Structural APPROVED
12/19/2023 Bldg Permits - Post Review Express PENDING ASSIGNMENT
12/13/2023 Commercial Electrical REQUIRES RESUBMIT Permit Review TC-COM-1223-02776 (400 S BROADWAY PL TUCSON, AZ 85710)
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received.
Code reference, 2018 International Building Code (IBC), 2017 National Electrical Code (NEC).

1. Provide separate circuits for the Pit lighting and receptacles, NEC 620.24(A). (SVC Pit LW-24)
2. Provide separate circuits for the Pit lighting and receptacles, NEC 620.24(A). (Glass Pit LW-26)

Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov
12/13/2023 Commercial Mechanical REQUIRES RESUBMIT 1. Provide a mechanical design for the proposed split system AC unit that clearly shows that the installation will comply with the requirements of Sections 304.1, 306.1, and 307, IMC 2018. Reference: Section 107.2.1, IBC 2018.
2. Show that the proposed HVAC equipment meets the minimum performance requirements of Section C403.3.2, IECC 2018 and the M1 Standards published by the Department of Energy for equipment to be installed after January 1, 2023.
3. Verify that the cooling capacity of the proposed split system AC unit will prevent overheating of the elevator equipment. Reference: Section 3005.2, IBC 2018.
12/05/2023 PDSD Application Completeness Express REVIEW COMPLETED