Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: TC-COM-1222-00390
Parcel: 132131260

Review Status: Requires Resubmit

Review Details: COMMERCIAL PDSD SIMPLE REVIEW v.2

Permit Number - TC-COM-1222-00390
Review Name: COMMERCIAL PDSD SIMPLE REVIEW v.2
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
03/14/2023 Bldg Permits - Post Review PENDING ASSIGNMENT
03/14/2023 Commercial Electrical REQUIRES RESUBMIT Please address the electrical plan review comments and provide a written response.

1 The resubmitted electrical plans need to show designated branch circuit and panel utilized for the sound system power.

2 Locate all receptacles and breaker panel on the electrical floor plan.

3 Provide a complete panel schedule.

4 Provide power requirements and system output specifications on the plans or include in the submittal documents.

Ref: 2018 IBC section 107.2.1, 2017NEC