Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL PDSD SIMPLE REVIEW v.2
Permit Number - TC-COM-1222-00390
Review Name: COMMERCIAL PDSD SIMPLE REVIEW v.2
Review Status: Requires Resubmit
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
03/14/2023 | Bldg Permits - Post Review | PENDING ASSIGNMENT | |||
03/14/2023 | Commercial Electrical | REQUIRES RESUBMIT | Please address the electrical plan review comments and provide a written response. 1 The resubmitted electrical plans need to show designated branch circuit and panel utilized for the sound system power. 2 Locate all receptacles and breaker panel on the electrical floor plan. 3 Provide a complete panel schedule. 4 Provide power requirements and system output specifications on the plans or include in the submittal documents. Ref: 2018 IBC section 107.2.1, 2017NEC |