Permit Number: TC-COM-1222-00342
Parcel: 12507170A

Address:
500 N TUCSON BL

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-1222-00342
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
01/26/2023 Bldg Permits - Post Review PENDING ASSIGNMENT
01/24/2023 External Reviewers - SAFEBuilt REQUIRES RESUBMIT Activity Number: TC-COM-1222-00342

GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.


STRUCTURAL REVIEW COMMENTS:
Denied
1. The engineer professional stamp on the structural sheets indicates that William Hill is a Civil not a structural engineer. Provide a stamp and seal from a structural engineer on the structural drawings and include the seals expiration date.
2. Provide a detail for how the new east side canopy will be attached to the structure on the drawings. The architectural plans indicate a 4” c-channel with 1/2” anchor bolts per structural. Note: There appears to be an existing window above door 108 that may interfere with the attachment.
3. Provide calculations for the East Elevation Canopy where there is a 5’ and a 7’ cantilever off each end, on the calculations for the main canopy could be found on the attached documents.


BUILDING REVIEW COMMENTS:
Denied
1. Update the project description on the cover sheet to include the work on the east side of the structure (only the north side work is listed) as well as the installation of the new storefront windows.
2. Verify the overall valuation of work for this project, the application indicates 200,000.00. this should include all work to be covered by this submittal.
3. Clarify the general notes listed on all sheets and verify they are applicable to this project. Note 10 is referencing a pool that does not appear to be indicated and note 9 is for interior work.
4. Verify the site conditions on the east side of the building on the plans, the site plans show angled parking and no sidewalk however the demo plan shows an existing straight sidewalk to remain. Indicate the other two existing roof scuppers on drawings and clarify if they are to be re routed or will remain surface discharge.
5. Indicate the existing electrical panels and other permanently installed structures on the east side of the building near door 109 on the plans.
6. Verify the new accessible route to and from the parking for door 107 on the drawings. It does not appear that door 107 will comply with the required clear space for a side approach or front approach. Provide additional dimensions for this door and the distance to the new column and sidewalk to verify compliance with ICC A117.1-2009 Figure 404.2.3.2.
7. Indicate on the drawing that the new sidewalk/ patio walking surface shall be stable firm and slip resistant and any changes in level shall comply with ICC A117.1-2009 Section 303.
8. Provide construction details for the removal and reframing of the rough opening for the existing window 109 that is to be enlarged vertically.
9. Clarify if the window above door 108 will be filled in and provide construction details for this work. Coordinate with the new canopy attachment.
10. Provide dimensions for the turn-downed/ thickened slab on the hardscape details on sheet A1.4 including the minimum width and depth requirements. Keynote 3 on this sheet indicates to coordinate with civil drawings however no civil were included in the set. Update the note.
11. Provide u values for windows that are in compliance with the 2018 IECC, the storefront notes on sheet A5.1 only indicate insulated glass panels with no values.


MECHANICAL REVIEW COMMENTS:
Conditionally Approved
No mechanical work has been included with this submittal


ELECTRICAL REVIEW COMMENTS
Denied
1. Provide an electrical plan for the project that indicates the location of the exiting lighting and receptacles to be removed, and the locations of the new electrical devices to be installed.
2. Provide a panel schedule for the electrical service panel that will be feeding the devices and indicates where that panel is located on the building.
3. Provide wiring methods, material, and wire sizes as well as applicable electrical notes for the new electrical devices.
4. Provide an outdoor lighting schedule and calculations that verify compliance with the City of Tucson/ Pima County Outdoor Lighting Code.
5. Provide an interior lighting COMcheck or other approved methodology for the project for the new proposed lighting that is in compliance with the 2018 IECC.
6. Indicate the location of an existing emergency light on the exterior at the exit doors to illuminate the landings or indicate new fixtures will be provided. 2018 IBC 1008.3.2 (5).


PLUMBING REVIEW COMMENTS:
Denied
1. Provide information on the rerouting of the existing irrigation system on the site drawing per keynote 16 on sheet A1.1 or indicate that this work will be done under a separate permit.


If you require additional clarification regarding these comments, please contact Doris Benoit at doris.benoit@tucsonaz.gov
01/26/2023 Site Engineering REQUIRES RESUBMIT See Zoning Comment
01/18/2023 Site Zoning REQUIRES RESUBMIT FROM: Paul Camarena
PDSD Zoning Review Section

PROJECT: TC-COM-1222-00342
500 N TUCSON BL Zoning C-1

TRANSMITTAL DATE:‎January 18, 2023


COMMENTS: Please resubmit revised drawings along with a detailed response letter, which states how all Zoning Review Section comments were addressed.

1.COMMENT: Zoning has reviewed the building plan for compliance with the unapproved DP22-0300, Zoning cannot approve the building plans until the DP is approved.


If you have any questions about this transmittal, Contact Paul Camarena at (520)837-4986 or by email Paul.Camarena@tucsonaz.gov
01/11/2023 Fire New Construction REVIEW COMPLETED
01/04/2023 PDSD Application Completeness REVIEW COMPLETED