Permit Number: TC-COM-1222-00318
Parcel: 10510081C

Address:
4225 N 1ST AV

Review Status: Requires Resubmit

Review Details: COMMERCIAL PDSD SIMPLE REVIEW v.3

Permit Number - TC-COM-1222-00318
Review Name: COMMERCIAL PDSD SIMPLE REVIEW v.3
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
04/26/2023 Bldg Permits - Post Review PENDING ASSIGNMENT
04/26/2023 Commercial Electrical REQUIRES RESUBMIT Please address the electrical plan review comments and provide a written response.

1 The format used to upload the revised electrical plan resulted in a non-legible plan. Resubmit the plan documents in a PDF format compatible with the COT program.

2 Previous electrical review comment not addressed. Justify the need for a separate electrical service in leu of using an existing house panel for the Branch Circuit to provide power for the Gate. Also, submit for Special Permission to install another electrical service for the Gate, NEC 230.2(A) - (D).

Ref; 2018 IBC section 107.2.1, 2017 NEC
03/30/2023 PDSD Application Completeness REVIEW COMPLETED