Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
01/26/2023 | Bldg Permits - Post Review | PENDING ASSIGNMENT | |||
01/26/2023 | Commercial Electrical | REQUIRES RESUBMIT | 1 Show all existing electrical services for this building in the site plan and verify compliance with NEC art 230.2. (By Special Permission). 2 Provide a grounding detail for the new electrical service. If there are multiple services for this building, provide compliance with NEC 250.58. (Common Grounding Electrode). Ref 2018 IBC section 107.2.1, 2017 NEC. |
||
12/23/2022 | PDSD Application Completeness | REVIEW COMPLETED |