Permit Number: TC-COM-1222-00315
Parcel: 12710084B

Review Status: Requires Resubmit

Review Details: COMMERCIAL PDSD SIMPLE REVIEW v.1

Permit Number - TC-COM-1222-00315
Review Name: COMMERCIAL PDSD SIMPLE REVIEW v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
01/04/2023 Bldg Permits - Post Review PENDING ASSIGNMENT
01/04/2023 Commercial Electrical REQUIRES RESUBMIT For clarity, please provide complete electrical plans and scope in detail of the proposed electrical work.

For example, the notes on the electrical plan call out to replace the existing 600 amp service disconnect with a ‘Service Entrance’ ….... Provide detailed information about the ‘Service Entrance’. Such as; (a) Secondary conduits, conductors quantity and types. (b) AIC ratings of electrical equipment. (c)Voltage, Phase, Amp rating of the ‘Service Entrance’, OCPD types and ratings. (d) Grounding detail. (e) New or existing panels and complete panel schedules if applicable. (f) Load calculations.(g) Is this a metered ‘Service Entrance’ Cabinet? Where is the utility meter located?

If necessary, obtain the services of an experienced Electrical Engineer to perform design and load calculations necessary to provide evidence on the plans that the installation meets all the requirements of the 2017 NEC.

Ref; 2018 IBC section 107.2, 2017 NEC, City of Tucson Commercial Plan Submittal Requirements.
12/23/2022 PDSD Application Completeness REVIEW COMPLETED