Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL PDSD SIMPLE REVIEW v.3
Permit Number - TC-COM-1222-00314
Review Name: COMMERCIAL PDSD SIMPLE REVIEW v.3
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 07/12/2023 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 07/12/2023 | Commercial Electrical | REQUIRES RESUBMIT | Please address the electrical plan review comments and provide a written response. The submitted site lighting plan and lumen calculations did not provide adequate information to verify complete compliance with the 2012 City of Tucson Outdoor Lighting Code (OLC). The following Code discrepancies are noted. Also Apply Code sections where applicable. As part of the lumen calculations, you must provide the correct lighting area and option used. At this address, the lighting area is E3, not E2. The option is not shown. This will have an effect on the lumen calculations. See table 401.1. The site plan must show an accurate location and inventory of both New and Existing exterior luminaires. (OLC) Section 102.4.2. Section 104.2.1 Lumen calculation on plans. There shall be documentation on the plans to demonstrate compliance with the lumen cap per Table 401.1, and which includes the following information: 1. Each exterior luminaire type with the lumens for that type, the quantity of each type and whether the luminaire is full cut-off or unshielded. 2. The total of full cut-off and unshielded lumens for the parcel. 3. A statement of the lighting area, the size of the permitted parcel, and the maximum allowed full cut-off and unshielded lumens. Exception to 104.2.1: In Lighting Areas E3, E3a and E2, when the total outdoor lighting installation is full cut-off lighting installed under canopies, roof overhangs or eaves, Lumen Calculation shall not be required. Section 104.2.2 Special inspection note. The plan submission shall contain a note indicating whether special inspection is required in accordance with Section 106. Section 106.2 Special inspection requirement. 106.2.1 Special inspection shall be required when the lumens per net acre are greater than 100,000 or 75% of the allowable lumens per Table 401.1, whichever is less. 106.2.2 Provide special inspection for all Recreational Facility lighting. 106.2.3 Provide special inspection for all Special Uses per Chapter 7. Section 401.3.1 Light trespass. Light fixtures on the residential side of commercial property adjacent to residential property shall be full cutoff and shall be installed not higher than 10 feet above grade at the property line and no higher than a line rising 20 degrees above the 10 feet until 100 feet from the property line, measured perpendicular to the lot line. Section 403.1 Unshielded Light Sources. Unshielded lighting shall be extinguished between 11:00 P.M. and sunrise the following day. Section 403.5 Outdoor Lighting Controls. 403.5.1 The means of controlling the specific “off” curfew shall be by a 24 hour timing device that includes stand-by power to maintain the time and program for a minimum of 6 hours. 403.5.2 Whenever any curfew “off” time is required by this Code, a permanent sign or notice shall be installed at the time control device stating the required turn-off time. Such sign or notice may be installed within the cover of the time control device such that it is visible whenever the device is set or adjusted. Suggested wording is as follows: “Set off time for Sign no later than 10:00PM MST in accordance with City of Tucson/Pima County Outdoor Lighting Code. Penalty for non-compliance per Outdoor Lighting Code Section 107.4. Penalties shall not exceed $750.00 for individuals and $10,000.00 for other legal entities.” (Adjust wording as needed for type of lighting to which curfew applies and the applicable curfew time.) Ref; 2012 City of Tucson Outdoor Lighting Code. Ordinance # 10963 |
||
| 06/26/2023 | PDSD Application Completeness Express | REVIEW COMPLETED |