Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-1222-00293
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
01/05/2023 Commercial Electrical APPROVED
01/25/2023 Site Engineering NOT REQUIRED
02/21/2023 Bldg Permits - Post Review PENDING ASSIGNMENT
02/21/2023 Commercial Building REQUIRES RESUBMIT For submittal purposes, customer ready to resubmit
02/01/2023 Commercial Mechanical REQUIRES RESUBMIT 1. The tenant-supplied laser equipment has an 8” exhaust duct with an unknown flow rate. Verify that the outside air supplied to the space is sufficient to provide make up air to replace the air exhausted. Reference: Section 501.4, IMC 2018.
2. The warehouse has a significant area occupied by printing equipment. Why will this equipment area not be required to be provided with ventilation as described in Table 403.3.1.1, IMC 2018 for printing rooms? Reference: Section 107.2.1, IBC 2018.
02/01/2023 Commercial Plumbing REQUIRES RESUBMIT Revise the design for mounting the shelf for the water heater (detail 3/P2.0) based on the wall type shown on the architectural drawings (i.e. steel studs rather than wood studs) and detail 14/A4.0. Reference: Section 301.2, IPC 2018.
01/12/2023 Site Zoning REQUIRES RESUBMIT Provide a use as classified per the UDC
01/23/2023 Fire New Construction REVIEW COMPLETED
12/30/2022 PDSD Application Completeness REVIEW COMPLETED