Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL REVIEW - FULL v.1
Permit Number - TC-COM-1222-00288
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
02/21/2023 | Commercial Building | APPROVED | |||
01/05/2023 | Commercial Electrical | APPROVED | |||
01/31/2023 | Commercial Plumbing | APPROVED | |||
01/12/2023 | Site Zoning | APPROVED | |||
01/25/2023 | Site Engineering | NOT REQUIRED | |||
02/21/2023 | Bldg Permits - Post Review | PENDING ASSIGNMENT | |||
01/31/2023 | Commercial Mechanical | REQUIRES RESUBMIT | Provide heating and cooling load calculations to justify the heating/cooling capacities of the specified HVAC unit. Reference: Section C403.1.1 and C502.2.3, IECC 2018. | ||
01/11/2023 | Fire New Construction | REQUIRES RESUBMIT | Plans shall show if the building has a fire sprinkler and or a fire alarm system. If so, please add a note that the fire sprinkler and fire alarm permits shall be submitted to TFD for permit. Jennifer Peel-Davis Tucson Fire Department Fire Plans Examiner Fire Inspector I, II and Fire Alarm Plans Examiner Jennifer.Peel-Davis@Tucsonaz.gov Desk: 520-837-7033 |
||
12/30/2022 | PDSD Application Completeness | REVIEW COMPLETED |