Permit Number: TC-COM-1222-00253
Parcel: 10605081A

Address:
3623 N ORACLE RD

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.4

Permit Number - TC-COM-1222-00253
Review Name: COMMERCIAL REVIEW - FULL v.4
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
08/31/2023 Bldg Permits - Post Review PENDING ASSIGNMENT
08/31/2023 Signs REQUIRES RESUBMIT Per BRC review: Below are comments on the authorized repair and authorized electrical repair resubmittal for COT ID# 493 at 3623 North Oracle Road (TC-COM-1222-0253).



Sheet 1 of 7

No comments.

Sheet 2 of 7

1 In the Panel Schedule, the revisions were not fully responsive to the 5/31/2023 Comment #2 on the prior submittal, as the v-a entries should be 954 v-a for Circuits #1 and #3 (for two lamps and including the added 25% factor); please revise these two entries and the associated v-a totals and note the these are the standard entries for this common configuration and were previously approved for this billboard under T10EL02028; also note that the 320W entry for the lamp description is a nominal figure and not the actual load specified by the manufacturer (Holophane).

2. Above Title Box, add a delta 1 with text “City of Tucson Comments 1/23/2023”, which was missing from the second submittal.

Sheet 3 of 7

1. In added 10th paragraph of Scope of Work, clarify that the referenced catwalk ledgers are the second from the west and that there are no catwalk ledger to upright bolt replacements under this plan (as appears to be the case from the Detail D location shown on the South Face Sign Elevation).

2. In added 11th paragraph of Scope of Work, add sentence clarifying that there bolts or other fasteners for attachment of the west end front catwalks to the first ledgers from the west or otherwise revise plan sheets to account for such fasteners.

3. In 10th boxed note, please revise for further clarification to read “Upright I-Beams will not be removed and reinstalled or replaced under this plan”.

4. Add boxed note: “Special inspection for high strength bolting required .Inspector must be on site during the entire bolting process and a special inspection report must be filed with PDSD? confirming that replacement of A325 bolts requires special inspection and a special inspection certificate must be filed with PDSD prior to final inspection approval:”.

Sheet 4 of 7

No comments.

Sheet 5 of 7

1. Add large cloud around outer perimeter of the seven added details with deltas 2 and 3 to clarify that the details were added with the third submittal and clouded with the subsequent submittal..

2. For added Detail C, add top view that specifies outer edge dimensions of the torsion saddle bottom plate and dimensions of hole centers to the outer edges.

3. For added Detail D, add top view that specifies outer edge dimensions of the upright bottom plates and dimensions of hole centers to the outer edges.

Sheet 6 of 7

No comments.

Sheet 7 of 7

No comments
08/09/2023 PDSD Application Completeness REVIEW COMPLETED