Permit Number: TC-COM-1222-00252
Parcel: 11941176H

Address:
1775 W AJO WY

Review Status: Approved

Review Details: COMMERCIAL REVIEW - FULL v.4

Permit Number - TC-COM-1222-00252
Review Name: COMMERCIAL REVIEW - FULL v.4
Review Status: Approved
Review Date Reviewer's Name Type of Review Description Status Comments
05/19/2023 External Reviewers - SAFEBuilt APPROVED Structural(S) Reviewer
Daljit Benipal
dbenipal@safebuilt.com
Conditionally Approved
Reason:
Date Completed : 3/14/2023 9:03:08 AM
NOTE: Every effort has been made to identify the code violations. Any oversight by the review team shall not be considered an authority to violate, set aside, cancel or alter applicable codes or ordinances. The plan review and permit issuance shall
not be considered a warranty or guarantee. The Structural Engineer is responsible for following ALL applicable Federal, State and local Municipal Codes and Ordinances.

Building(B) Reviewer
Don Wilkins
dwilkins@safebuilt.com
Approved
Reason:
Date Completed : 5/17/2023 2:15:25 PM

Mechanical(M) Reviewer
Neil Samaan
nsamaan@safebuilt.com
Conditionally Approved
Reason:
Date Completed : 3/7/2023 10:37:22 PM

Approved/subject to field approval


Electrical(E) Reviewer (from previous submittal TUC8929001.030723)
Ron Ross
rross@safebuilt.com
Conditionally Approved
Date Completed : 3/17/2023 12:38:25 PM
2nd Electrical Review

E202 ELECTRICAL FLOOR PLAN - BUILDING B/C AND E/F: Missing walls, receptacles in air. Specifically, rooms 159 and 160 are missing walls. Many other areas too.

Plumbing(P) Reviewer
Perry Hendershott
phendershott@safebuilt.com
Conditionally Approved
Reason:
Date Completed : 4/12/2023 7:57:42 PM
Third Plumbing Review: Ok subject to field inspections
1).OK Subject to Field Inspections: Plan page A130 needs to illustrate the roof drainage method and sizing calculations -IPC 1106.1, 1106.2, 1108 **all roof areas existing to remain per response**
7) OK- Water Heater Combustion air & exhaust subject to Field inspections & manufacturer specs
10). OK- Cafe area not required to drain thru a grease interceptor per local utility authority see uploaded letter. ** Subject to Field Inspections**
05/09/2023 Site Zoning APPROVED
05/19/2023 Bldg Permits - Post Review REVIEW COMPLETED
05/08/2023 PDSD Application Completeness REVIEW COMPLETED