Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL REVIEW - FULL v.1
Permit Number - TC-COM-1222-00237
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 04/25/2023 | External Reviewers - Stantec | APPROVED | |||
| 01/05/2023 | Site Engineering | APPROVED | |||
| 01/03/2023 | Site Zoning | APPROVED | |||
| 04/25/2023 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 01/10/2023 | Fire New Construction | REQUIRES RESUBMIT | -Fixed seating in dining room and patio not calculated correctly. Redesigned seating from T21CM09437 showed an interior occupant load of 82. New occupant load inside is showing as 72 by removing some seating. Booths are still installed, and the bar stools can be added back by the customer. Customer advised under T21CM09437 not to occupy the patio. Patio online appears to be occupied. Booths designed for 3-4 occupants not calculated correctly. Provide correct occupant load per IFC 2018, Chapter 10, Table 1004.5 and if 100+ install fire sprinklers. Questions: Jennifer Peel-Davis Tucson Fire Department Fire Plans Examiner Fire Inspector I, II and Fire Alarm Plans Examiner Jennifer.Peel-Davis@Tucsonaz.gov Desk: 520-837-7033 |
||
| 12/13/2022 | PDSD Application Completeness Express | REVIEW COMPLETED |