Permit Number: TC-COM-1222-00232
Parcel: 13323190A

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-1222-00232
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
12/13/2022 Site Zoning APPROVED
01/04/2023 Site Engineering NOT REQUIRED
01/20/2023 Bldg Permits - Post Review PENDING ASSIGNMENT
01/20/2023 External Reviewers - SAFEBuilt REQUIRES RESUBMIT Activity Number: TC-COM-1222-00232


GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.


STRUCTURAL REVIEW COMMENTS:
CONDITIONALLY APPROVED
NOTE: Every effort has been made to identify the code violations. Any oversight by the review team shall not be considered an authority to violate, set aside, cancel or alter applicable codes or ordinances. The plan review and permit issuance shall not be considered a warranty or guarantee. The Structural Engineer is responsible for following ALL applicable Federal, State and local Municipal Codes and Ordinances.


BUILDING REVIEW COMMENTS:
APPROVED
Approved per the following:
Every effort has been made to identify the code violations. Any oversight by the review team shall not be considered an authority to violate, set aside, cancel, or alter applicable codes or ordinances. The plan review and permit issuance shall not be considered a warranty or guarantee. The registered design professional is responsible for following ALL applicable Federal, State, and local Municipal Codes and Ordinances.


MECHANICAL REVIEW COMMENTS:
CONDITIONALLY APPROVED
Approved/subject to field approval


ELECTRICAL REVIEW COMMENTS
APPROVED

PLUMBING REVIEW COMMENTS:
DENIED
First Plumbing Review:
1). Floral Prep sink on plan page P1.1 needs hot water--IPC 607.1
2). Condensate from AHU1 (1.5 Ton) on plan page P1.1 can't discharge to a floor sink connected to the grease system. - IPC 1003.2


If you require additional clarification regarding these comments, please contact Doris Benoit at doris.benoit@tucsonaz.gov
01/09/2023 Fire New Construction REVIEW COMPLETED
12/12/2022 PDSD Application Completeness REVIEW COMPLETED