Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL REVIEW - FULL v.1
Permit Number - TC-COM-1222-00231
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
01/19/2023 | Commercial Building | APPROVED | |||
01/19/2023 | Commercial Electrical | APPROVED | |||
01/19/2023 | Commercial Plumbing | APPROVED | |||
12/21/2022 | Site Zoning | APPROVED | |||
01/05/2023 | Site Engineering | NOT REQUIRED | |||
01/19/2023 | Bldg Permits - Post Review | PENDING ASSIGNMENT | |||
01/19/2023 | Commercial Mechanical | REQUIRES RESUBMIT | 1. The treatment rooms are identified as “beauty and nail salons” in the outdoor air calculation. Footnote b on Table 403.3.1.1, IMC 2018 states that mechanical exhaust is required for the beauty salon and no air from the salon may be recirculated to any other space. FC-1 appears to be recirculating air from the salon area (320 square feet) to the remaining 770 square feet of the suite. Clarify the nature of the operations occurring in the treatment rooms and adjust the mechanical design as needed. Reference: Section 403.2.1 (3), IMC 2018. 2. The air supplied to the waiting and reception rooms is returned to FC-1 via a return air grille located at the east end of the corridor. Revise the mechanical design as required to avoid using the corridor as a return air duct. Reference: Section 601.2, IMC 2018. |
||
01/10/2023 | Fire New Construction | REVIEW COMPLETED | |||
12/14/2022 | PDSD Application Completeness | REVIEW COMPLETED |