Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-1222-00231
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
01/19/2023 Commercial Building APPROVED
01/19/2023 Commercial Electrical APPROVED
01/19/2023 Commercial Plumbing APPROVED
12/21/2022 Site Zoning APPROVED
01/05/2023 Site Engineering NOT REQUIRED
01/19/2023 Bldg Permits - Post Review PENDING ASSIGNMENT
01/19/2023 Commercial Mechanical REQUIRES RESUBMIT 1. The treatment rooms are identified as “beauty and nail salons” in the outdoor air calculation. Footnote b on Table 403.3.1.1, IMC 2018 states that mechanical exhaust is required for the beauty salon and no air from the salon may be recirculated to any other space. FC-1 appears to be recirculating air from the salon area (320 square feet) to the remaining 770 square feet of the suite. Clarify the nature of the operations occurring in the treatment rooms and adjust the mechanical design as needed. Reference: Section 403.2.1 (3), IMC 2018.
2. The air supplied to the waiting and reception rooms is returned to FC-1 via a return air grille located at the east end of the corridor. Revise the mechanical design as required to avoid using the corridor as a return air duct. Reference: Section 601.2, IMC 2018.
01/10/2023 Fire New Construction REVIEW COMPLETED
12/14/2022 PDSD Application Completeness REVIEW COMPLETED