Permit Number: TC-COM-1126-01811
Parcel: 11450004K

Review Status: In Review

Review Details: COMMERCIAL REVIEW - LIMITED v.1

Permit Number - TC-COM-1126-01811
Review Name: COMMERCIAL REVIEW - LIMITED v.1
Review Status: In Review
Review Date Reviewer's Name Type of Review Description Status Comments
11/16/2026 Site Engineering APPROVED A floodplain use permit (TE-FPU-1126-00455) has been created to allow for work with in the floodplain. See it for fees and additional details.
11/23/2026 Water - PDSD APPROVED
N/A Commercial Building PENDING ASSIGNMENT
N/A Fire New Construction PENDING ASSIGNMENT
N/A Site Zoning PENDING ASSIGNMENT
11/19/2026 Commercial Electrical REQUIRES RESUBMIT Commercial Electrical Review TC-COM-1126-01811 (8300 E TANQUE VERDE RD TUCSON, AZ 85749)
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received.
Code reference, 2024 International Building Code (IBC), 2023 National Electrical Code (NEC), 2012 Outdoor Lighting Code (OLC).
https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/building-code/2012_outdoor_lighting_code_.pdf

Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov


1. Provide an electrical plan showing any/all electrical work. Plans shall include but may not be limited to items below and as necessary for the actual scope of work:
2. Provide electrical sheets sealed, dated and signed by an Arizona Registered Electrical Engineer.
3. Electrical demo plans.
4. Provide an electrical panel schedule and designate the circuit number on the electrical plans, that corresponds to the panel schedule, at the location of each, new or modified light fixture, receptacle, and equipment disconnect switch, NEC arts;300 and 408.4. IBC 107.1.
5. Provide electrical load calculations, for the Main Service Panel, Per NEC 220.40.
6. Provide a line diagram showing the new equipment being added or modified, NEC 110.2, 2018 IBC 107.1.
7. Show all wiring methods in detail for all new or modified branch circuit conductors and feeders. Conductor type and conduit size/type. Note wet use requirements. NEC arts;300 and 408.4.
11/23/2026 Commercial Mechanical REQUIRES RESUBMIT 1. Provide construction documents that are complete and clearly indicate the extent of the proposed work (i.e. not with the “plans are not intended for construction use” label). Reference: Section 107.2.1, IBC 2024.
2. Provide a mechanical design and calculations performed by an Arizona registrant who has demonstrated proficiency through registration, education, technical knowledge, or experience to perform such work. Reference: Sections 107.1 and 107.2.1, IBC 2024.

If you have any questions about this review comment, I can be reached at Robert.Sherry@tucsonaz.gov.
11/23/2026 Commercial Plumbing REQUIRES RESUBMIT 1. Provide construction documents that are complete and clearly indicate the extent of the proposed work (i.e. not with the “plans are not intended for construction use” label). Reference: Section 107.2.1, IBC 2024.
2. Provide a plumbing design and calculations performed by an Arizona registrant who has demonstrated proficiency through registration, education, technical knowledge, or experience to perform such work. Reference: Sections 107.1 and 107.2.1, IBC 2024.
If you have any questions about this review comment, I can be reached at Robert.Sherry@tucsonaz.gov
11/12/2026 PDSD Application Completeness Express REVIEW COMPLETED