Review Date Reviewer's Name Type of Review Description Status Comments
N/A Commercial Building Standard PENDING ASSIGNMENT
N/A Commercial Mechanical Standard PENDING ASSIGNMENT
N/A Commercial Plumbing Standard PENDING ASSIGNMENT
N/A Commercial Post Review Express PENDING ASSIGNMENT
N/A Fire New Construction Standard PENDING ASSIGNMENT
N/A Site Engineering Standard PENDING ASSIGNMENT
N/A Site Zoning Standard PENDING ASSIGNMENT
N/A Water - PDSD Standard PENDING ASSIGNMENT
11/25/2026 Commercial Electrical Standard REQUIRES RESUBMIT Commercial Electrical Review TC-COM-1126-01795 (10040 E OLD VAIL RD TUCSON, AZ 85747)
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received.
Code reference, 2024 International Building Code (IBC), 2023 National Electrical Code (NEC), 2012 Outdoor Lighting Code (OLC).
https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/building-code/2012_outdoor_lighting_code_.pdf

Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov

1. Reference Sheet E2.2, Detail 1, Ice Machine Alcove. Provide GFCI protection for all receptacles in an indoor wet or damp area per NEC 210.8(B)(8).
2. Reference Sheet E2.2, Detail 2, UPC Racks. These circuits are missing the panel designation. Please provide panel designation with the circuit numbers.
3. Provide one GFCI protected receptacle within 25' of all indoor electrical equipment that require service/maintenance (switchgear, panelboards, transformers etc.) per NEC 210.63(B)(2), and per NEC 210.8(E).
4. Provide a minimum of one service receptacle, with GFCI protection, within Electrical Room 1, NEC 210.63(B)(2), NEC 210.8(E).
5. Reference Sheet E3.1, Detail 4, 3.Note or show conduit through the roof with sealant and Expansion joints as needed for Raceway exposed to different temperatures, NEC 300.7(A) & (B). (Comment may apply to additional details and penetrations)
6. Reference sheet E4, EGC from transformer T4D2 is undersized for the 600A Overcurrent Device, NEC Table 250.122.
7. Reference Sheet E4 & E4.3, Panel LPU and Transformer TPU. Provide overcurrent protection for Panel LPU per NEC 408.36 and for the transformer secondary conductors Per NEC 240.21, or provide compliance method used per NEC 240.21(C).
8. Reference sheet E4, EGC from transformer T1D is undersized for the 400A Overcurrent Device, NEC Table 250.122.
9. Reference Sheet E4 & E4.1, MSB1 & MSB2 Overcurrent protection devices. The panel schedule on Sheet E4.1 shows 2,500A BRKRs for each MSB1 & MSB2, while the line diagram on sheet E4 shows 3,000AF/2,000AT. Please coordinate and show consistent size/settings.
10. Reference Sheet GE2, Kitchen units D059F, circuits L4D2 44,46,46 & 60,62,64. Provide GFCI protection for all receptacles within the kitchen area per NEC 210.8(B)(2). Readily accessible per 210.8. (All receptacles supplied by three-phase branch circuits rated 150 volts or less to ground, 100 amperes or less,)
11. Note or show all conduits passing into or out-of the walk-in freezer/cooler units, with sealant and expansion joints per NEC 300.7(A) & (B). Provide details as necessary. Comment applies to all penetrations into freezer/cooler where conduit is exposed to different temperatures.
11/23/2026 Outdoor Lighting Standard REQUIRES RESUBMIT Outdoor Lighting Review TC-COM-1126-01795 (10040 E OLD VAIL RD TUCSON, AZ 85747)
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received.
Code reference, 2024 International Building Code (IBC), 2023 National Electrical Code (NEC), 2012 Outdoor Lighting Code (OLC).
https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/building-code/2012_outdoor_lighting_code_.pdf

Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov

1. The replacement, relocation and installation of new lighting fixtures requires compliance with the City of Tucson Outdoor Lighting Code.
2. Site lighting and electrical cannot be reviewed, approved or installed under the Development Package permit and must be included in a construction permit.
3. Provide an outdoor lighting plan that meets the requirements of OLC 104.2. Show/locate the different outdoor light sources on your lighting plan, both new and existing. Number the light fixtures on your lighting fixture table and use the same number on your site plan.
4. List the Lighting Area per OLC (typically E3) chapter 3 and used in Table 401.1. Specify the compliance option from Table 401.1 that is being used. Total outdoor light output shall not exceed the lumen limits listed in Table 401.1.
5. Show compliance with City of Tucson Outdoor Lighting Code with an approved lighting calculation in accordance with OLC 104.2.1, 401.2. Include all exterior fixtures on the property in the calculations. List shielded and unshielded lights in the calculation.
6. Show unshielded fixtures with a maximum of 3,000 lumens, OLC 401.4.
7. Show lamps with a maximum of 3500K color temperature, OLC 402.1.
8. Provide the manufacturer’s specification sheets for the outdoor lighting fixtures. Include the lumen and color temperature values for each outdoor fixture type.
9. Indicate whether or not a special inspection is required per sec. 104.2.2, and 106.2.

https://www.tucsonaz.gov/files/sharedassets/public/v/1/city-services/planning-development-services/documents/special_inspection_certificate_odl.pdf

10. Specify any exceptions used.

11. Provide Curfew lighting controls If applicable Per section 403.
11/06/2026 PDSD Application Completeness Express REVIEW COMPLETED