Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL REVIEW - FULL v.5
Permit Number - TC-COM-1125-02124
Review Name: COMMERCIAL REVIEW - FULL v.5
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 03/02/2026 | Commercial Plumbing Standard | APPROVED | |||
| 03/02/2026 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 03/02/2026 | Fire New Construction Standard | REQUIRES RESUBMIT | You did not address the previous fire comments. My comments are in regards to the fire alarm and not the fire sprinklers. 1. Indicate if the building has an existing fire alarm that will be modified or if a new fire alarm system will be installed throughout the building. Make these notes on the cover sheet or in the code analysis. Fire alarm is required, 2024 IFC 907.2.2 #2. john.vincent@tucsonaz.gov 5203495581 |
||
| 02/05/2026 | PDSD Application Completeness Express | REVIEW COMPLETED |