Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.5

Permit Number - TC-COM-1125-02124
Review Name: COMMERCIAL REVIEW - FULL v.5
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
03/02/2026 Commercial Plumbing Standard APPROVED
03/02/2026 Bldg Permits - Post Review Express PENDING ASSIGNMENT
03/02/2026 Fire New Construction Standard REQUIRES RESUBMIT You did not address the previous fire comments. My comments are in regards to the fire alarm and not the fire sprinklers.
1. Indicate if the building has an existing fire alarm that will be modified or if a new fire alarm system will be installed throughout the building. Make these notes on the cover sheet or in the code analysis. Fire alarm is required, 2024 IFC 907.2.2 #2.